Appendix, Wiring tables – Liquid Controls LCRII Install E3650-E3651 Series User Manual
Page 37
![background image](/manuals/336496/37/background.png)
Wiring Tables
This appendix provides a tabular description of the wiring connections made to each LCR-II terminal block. It should
be referenced in the event wiring is inadvertently mis-routed in the field, or for general troubleshooting in the event of
a problem.
Pull-down resistors of 300 Ω needs to be connected between
CHAN B and GND, and CHAN A and GND.
To operate a single channel pulser, a jumper is required between
pins 2 and 3 on J4.
sInGle Channel PUlseR (j8)
Terminal
Pin
signal
Wire Color
Route To
J8-38
37
GND
N/A
Pulser Signal GND
36
35
34
33
In 4
N/A
Pulse Output
32
31
+Vo
Red
+V Input
veedeR RooT solId sTaTe QUad PUlseR
(j8)
Terminal
Pin
signal
Wire Color
Route To
J8-38
37
GND
White
Pulser Signal GND
36
35
34
In 3
Orange
Channel B Output
33
In 4
Black
Channel A Output
32
31
+Vo
Red
+V Input
aUxIlIaRy oUTPUTs (j12)
Terminal
Pin
signal
Wire Color
Route To
J12-45
+Vo
N/A
44
Out 1
Aux. 1
N/A
Pump or Aux. Control
43
Out 2
Aux. 2
N/A
Flow Direction
42
Out 3
N/A
Pulse Input for Aux.
System
41
GND
N/A
40
Out 4
N/A
Display Input
39
Out 5
N/A
Display Input
valve solenoId ConneCTIon (j13)
Terminal
Pin
signal
Wire Color
Route To
J13-19
Earth
Green
Solenoid 2 Case
Ground
18
Out 6
Black or Red
Solenoid 2
17
+Vo
Black or Red
Solenoid 2
16
Earth
Green
Solenoid 1 Case
Ground
15
Out 7
Black or Red
Solenoid 1
14
+Vo
Black or Red
Solenoid 1
RTd TeMP. PRobe ConneCTIon (j14)
Terminal
Pin
signal
Wire Color
Route To
J14-23
RTD-D
Red
RTD
22
RTD-S
Red
RTD
21
RTD+D
White
RTD
20
RTD+S
White
RTD
oPTICal aIR elIMInaToR (j15)
Terminal
Pin
signal
Wire Color
Route To
J15-56
+Vo
Red
Optical Sensor
55
In 5
White
Optical Sensor
54
GND
Black
Optical Sensor
53
Out 8
Black
Solenoid 3
52
+Vo
Red
Solenoid 3
37