FS10 Series

Fluid Components International LLC

21

8

Hysteresis

Applied

Above or

Below Trip

Point

1111111100

- +

RELAY_HYSTERESIS_

EFFECT

0000011111 = apply

above

1111100000= apply

below

Selects whether the hysteresis is to be

applied above (default) or below the

relay trip point. Pressing the buttons will

toggle between the two options.

9

Maximum

Hysteresis

Value

1111111110

- +

RELAY_HYSTERESIS

1 – indicates current

value relative to

maximum 10%

hysteresis (MAX_

HYSTERESIS)

Buttons adjust the value of the dead

band effect. Increments in 1 percent

of trip-point value. Default setting is

2% of trip-point. Button range 0-10%.

Wider range available through RS232

interface.

10

Time Delay

to

Activate

Relay or

Binary Pulse

1111111111

- +

RELAY_TURN_ON_

DELAY

1 – indicates current

value relative to

maximum delay

(MAX_DELAY)

Time delay from when flow

measurement is greater/less than relay

trip point, to turn on relay. Increments

and decrements in 1 second steps [Max

default setting 10 seconds when using

buttons].*

11

Time Delay

to

De-activate

Relay or

Binary Pulse

1000000001

- +

RELAY_TURN_OFF_

DELAY

1 – indicates current

value relative to

maximum delay

(MAX_DELAY)

Time delay from when flow

measurement is greater/less than relay

trip point, to turn off relay. Increments

and decrements in 1 second steps [Max

default setting 10 seconds when using

buttons].*

12

Alarm

Simulation

1100000001

- +

0000011111= output

“max”

1111100000= output

“min”

Alarm simulation mode. Pressing the “+”

button forces “maximum” (corresponds

to A_OUT_DAC_COUNT_100) 4-20 mA

output. Pressing “-” forces “minimum”

(corresponds to A_OUT_DAC_

COUNT_0) 4-20 mA output.

Relay output will correspond with

RELAY_POLAR setting.

13

Keypad

Lockout

1110000001

- +

BTN_ENTER_TIMEOUT

1111100000 = 3

seconds

0000011111= 10

seconds

Keypad lockout time. Pressing the

buttons toggles between either 3

seconds or 10 seconds to hold both

buttons to enter “function selection”

mode.

14

Filter

Setting

1111000001

- +

INPUT_FILTER_COUNT

LED 1 on = setting 3

LEDs 1-3 on = 18

LEDs 1-5 on = 30

LEDs 1-7 on = 50

LEDs 1-10 on = 100

Input filtering count: Default = 18.

“-” decreases filter, min. = 3.

“+” increases filter, max. = 100.

Filter value 18 reduces response

time <2 sec

15

Save To

Bank

1111100001

- +

1111111000=7

User preset. Save current active

parameters (in 0 bank) to user bank

location 7. (Hint- use “-” button to

quickly move to FUNCTION 15 from

FUNCTION position 1). **

* Maximum time delay may be up to 65,000 seconds when using RS232 command line or PC interface.
** Function #4 (load a bank) and function #15 (save to a bank), requires holding either button for 3 seconds to load or save.

Holding both buttons will exit either function without performing the operation.