configuration level - parameters menu

All settings may influence the correct running of the process.

Note the values of the parameters set in the table at chap. 9.8.

function

Description of the function

UNIT (see chap. 9.5.1)

To select the unit of the flow rate.

KFAC (see chap. 9.5.2)

To enter the K factor of the fitting used or have it determined. The K factor is specific to each fitting. It is used by
the device to convert the measured signal into a flow rate.

OUT (see chap. 9.5.3)

• To select:

- the operation of the transistor or relay output (Hysteresis or Window);

- whether the operation is inverted or not.

• To set:

- the high (

O HI

) and low (

O LO

) switching thresholds;

- the time delay before switching in seconds (

DEL

).

mA (see chap. 9.5.4)

To set the flow rate range associated to the 4-20 mA output.

FILT (see chap. 9.5.5)

• To choose the filter of the displayed flow rate.
Filter 0 means that flow rate variations are displayed.
Filter 9 means that flow rate variations are attenuated to the maximum.

BRGR (see chap. 9.5.6)

To enter the flow rate range, minimum (

BG LO

) and maximum (

BG HI

) values, associated to the bar graph.

BKLG (see chap. 9.5.7)

To deactivate the backlighting of the display, or adjust its intensity and set the time-out after which it goes off.

CODE (see chap. 9.5.8)

To activate the use of the access code to the Parameters and Test menus. By default, the access code is not
requested.

END (see chap. 9.5.9)

To go back to the Process level by saving or not the settings made.