Description of the name plate, Technical data, Conditions of use – Burkert Type 8072 User Manual
Page 10: Compliance to standards and directives

8
Technicaldata
5.4.
Description of the name plate
FLOW : SE32
HALL
SUPPLY:12-36V= 90mA
REL:230V 3A
PV:12-36V / 4-20mA
0.3-10m/s
S-N:1110
00560547
W45LP
Made in France
2
3
4
6
8
10
7
5
1
9
11
1.
Measured process value and type of the electronic module
2.
Type of sensor
3.
Power supply; Max. current consumption
4.
Data of the on/off output
5.
Data of the current output
6.
Conformity logo
7.
Electrical protection class: double insulation
8.
Manufacturing code
9.
Measurement range of the flow rate
10.
Order code
11.
Serial number
Fig. 1:
Name plate (example)
6.
TechnicAl DATA
6.1.
conditions of use
Ambient temperature
• 8032
• 8072
• UL device
(in operation)
• -10°C...60°C
• 0°C...60°C
• 0°C...40°C
Air humidity
< 80%, non condensated
Height above sea level 2000 m max. (UL device)
Degree of pollution
Degee 2 acc. to EN 61010-1 (UL device)
Installation class
Class I acc. to UL 61010-1 (UL device)
Protection rating
IP65 acc. to EN 60529, with connectors
plugged-in and tightened or sealed
6.2.
compliance to standards and
directives
The device conforms to the EC directives through the following
standards:
• EMC: EN 61000-6-2, EN 61000-6-3
• LVD: EN 61010-1
• Environnemental testing: Vibration: EN 60068-2-6, Shock:
EN 60068-2-27.
• Pressure: The S030 fitting complies with article 3 of §3 from
97/23/CE directive.
English
Technical data