Maintenance of components, Ul handling, Maintenance of components 9.3 – Burkert Type 8644 User Manual
Page 64
64
Maintenance, Troubleshooting
Malfunction
possible cause
remedial action
Valves switch with
a delay or blow off
at the deaeration
connections
Inadequate or no pressure supply
Design the pressure supply with the largest
→
possible volume (even for upstream devices
such as pressure controllers, maintenance
units, shut-off valves, etc.)
Minimum operating pressure ≥ 2.5 bar
Valves are not in home position
(de-energized) during pressure
build-up
Pressurize the valve block before you switch
→
the valves.
Deaeration of the exhaust air ducts
inadequate due to too small or dirty
silencers (back pressures).
Use appropriately sized silencers or
→
expansion tanks. Clean dirty silencers.
Impurities or foreign objects in the
pilot valve or main valve
Change the valve.
→
Leaking valve blocks
Missing or crushed O-rings
between the modules;
Missing or incorrectly positioned
profile seals between valve and
pneumatic base module
Determine the leaks or missing seals.
→
Insert missing seals or replace damaged
→
seals.
Maintenance of components
9.3.
ul handling
9.3.1.
Valve clusters of Type 8644 with UL license may be converted by UL-certified production, installation, or service
centers only.
Do not reach into the system. This refers in particular to:
Damage of components,
•
Expansion of the valve clusters by modules; the catch mechanism of the pneumatic modules must be released
•
for this.
NoTE!
Replacement of the valves is a permitted maintenance operation; follow the general safety instructions.
Typ 8644
deutsch