Technical data of the valve block – Burkert Type 8644 User Manual
Page 18
18
Technical Data
Max. power consumption
Logic current
I_Log = I_Log_FBKN + Σ I_Module
I_Log
Power consumption in the 5 V - logic area
I_Log_FBKN
Proportionate current in the field bus node
(see relevant explanation in Wago documentation type)
Further product-specific information on Wago field bus nodes / terminals can be found on the Internet
under:
I_Module
Proportionate current in the 5 V - logic area of the electronic base modules
max 15 mA
I_Valve
Valve flow - before and after power reduction
feld bus node
see Wago handbook
The permitted ambient temperature depends on the modules used. The most critical module is essential
during assembly.
Module with: Valve Type: 6524, 6525, 6526, 6527
0 ... +55° C
Module with: Valve Type: 0460, 0461
0 ... +50° C
6.3.
Technical data of the valve block
Nominal operating mode
Long-term operation (100 % ED)
Protection class (in terminal design) IP20
Protection class
3 in accordance with VDE 0580
Total current
depends on electrical connection technology, expansion stage and control
add-on dimension
11 mm
Operating principle
Valve
C/D (3/2-way)
Type 6524
2xC (2 x 3/2-way)
Type 6524
L/N (5/3-way)
Type 0460***
Operating principle
Valve
H (5/2-way)
Type 6525
-
H (5/2-impulse)
Type 0460
flow-rate
300 l/min
300 l/min
200 l/min
pressure range
(with p shut-off)
2.5 ... 7 bar
5 ... 7 bar
2.5 ... 7 bar
-
2.5 ... 7 bar
-
Output
1 W
*
2 x 1 W
with power reduction
0.9 W
current before
power reduction
43 mA
2 x 43 mA
41 mA
current after
power reduction
28 mA
2 x 18 mA
-