Technical data, Operating conditions, Technical data of the entire system – Burkert Type 8644 User Manual

Page 17: Operating conditions 6.1

background image

17

Technical Data

6.

Technical daTa

Operating conditions

6.1.

WArNINg!

risk of injury!

Malfunction if used outside!

Do not use Type 8644 AirLINE system outdoors and avoid heat sources which may cause the permitted tem-

perature range to be exceeded.

permitted temperatures

Storage temperature:

-20 ... +60 °C

Permitted air humidity:

75% on average, 85% occasionally

Permitted air pressure

Operation:

80 kPa to 106 kPa (up to 2 000 m above sea level)

Storage / transport:

70 kPa to 106 kPa (up to 3 000 m above sea level)

Protection class:

Class 3 in accordance with VDE 106, IEC 60536

Protection class:

IP20 in accordance with IEC 60529

6.2.

Technical data of the entire system

electrical power supply

Nominal voltage

24 V / DC

Tolerance

-15 % / +20 %

Valve Types: 0460, 0461

-10 % / +10 %

Valve Type: 6524 (2 x 3/2-way)

-15 % / +10 %

current carrying capacity

Valve block (via connection module on front):

max. 2.5 A

Valve type

Valve flow

Before power reduction

after power reduction

6524

43 mA

28 mA

6524 (2 x 3/2-way)

43 mA

18 mA

6525

43 mA

28 mA

6526

85 mA

52 mA

6527

85 mA

52 mA

0460

41 mA

-

0461

41 mA

-

Typ 8644