Technical data, Operating conditions, Technical data of the entire system – Burkert Type 8644 User Manual
Page 17: Operating conditions 6.1
17
Technical Data
6.
Technical daTa
Operating conditions
6.1.
WArNINg!
risk of injury!
Malfunction if used outside!
Do not use Type 8644 AirLINE system outdoors and avoid heat sources which may cause the permitted tem-
•
perature range to be exceeded.
permitted temperatures
Storage temperature:
-20 ... +60 °C
Permitted air humidity:
75% on average, 85% occasionally
Permitted air pressure
Operation:
80 kPa to 106 kPa (up to 2 000 m above sea level)
Storage / transport:
70 kPa to 106 kPa (up to 3 000 m above sea level)
Protection class:
Class 3 in accordance with VDE 106, IEC 60536
Protection class:
IP20 in accordance with IEC 60529
6.2.
Technical data of the entire system
electrical power supply
Nominal voltage
24 V / DC
Tolerance
-15 % / +20 %
Valve Types: 0460, 0461
-10 % / +10 %
Valve Type: 6524 (2 x 3/2-way)
-15 % / +10 %
current carrying capacity
Valve block (via connection module on front):
max. 2.5 A
Valve type
Valve flow
Before power reduction
after power reduction
6524
43 mA
28 mA
6524 (2 x 3/2-way)
43 mA
18 mA
6525
43 mA
28 mA
6526
85 mA
52 mA
6527
85 mA
52 mA
0460
41 mA
-
0461
41 mA
-
Typ 8644