Electricalinstallation
9.2.1. Electrical installation with cable gland
Procedure:
→
The screw-type terminals can be accessed by unscrewing the
body casing (stainless steel).
→
Push the cables through the cable gland.
→
Connect the wires.
1
2
2)
3
2)
4
5
6
7
Fig. 9:
Screw-type terminals
Terminal
Configuration
1
Binary input +
2
2)
Analogue position feedback +
3
2)
Analogue position feedback GND
4
Set-point value +
(0/4 - 20 mA)
5
Set-point value GND
6
Supply voltage +
24 V DC
7
Supply voltage
GND
Tab. 3: Electrical installation with cable gland
2)
only optional
Seal
Body casing
Body casing
Fig. 10: Position of the seal in the body casing
→
Check that the seal is correctly positioned in the body casing.
NOTE!
Damage or malfunction due to penetration of dirt and humidity!
To ensure protection class IP65 / IP67:
• Tighten the union nut on the cable gland according to the cable
size or dummy plugs used (approx. 1.5 Nm).
• Screw the body casing in all the way.
→
Tighten union nut on the cable gland (torque approx. 1.5 Nm).
→
Close the device (assembly tool: 674077
3)
).
When the supply voltage is applied, the positioner is operating.
→
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2. Automatic adjustment X.TUNE”.
3)
The assembly tool (674077) is available from your Bürkert sales office.