6 display elements as-interface – Burkert Type 8691 User Manual
Page 22
22
Electrical installation
9.6 Display elements aS-interface
note!
Breakage of the pneumatic connection pieces due to rota-
tional impact.
▶ When unscrewing and screwing in the transparent cap, do not
hold the actuator of the process valve but the connection housing.
Pilot valve LED yellow
Bus LED green
Bus LED red
Status LED yellow
Top LEDs
Jumper: Color
assignment of
the Top LEDs
Connection housing
Fig. 18: Display elements AS-Interface
note!
damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the trans-
parent cap in all the way.
Bus led
(green)
Bus led
(red)
off
off
POWER OFF
off
on
No data traffic (expired Watch Dog at slave
address does not equal 0)
on
off
OK
flashing
on
Slave address equals 0
off
flashing
Sensor supply overloaded or external reset
flashing
flashing
Teach function error (Periphery error)
Tab. 6: Display elements bus status
led
color
Status LED
flashing yellow
Teach function is running
flickers yellow
Puck PCB not available
Top LEDs
4)
is lit green
End postion bottom
is lit yellow
End postion top
flashing red
alternately with the
green or yellow
no data traffic or
teach function error
LED
Pilot valve
is lit yellow
Pilot valve is actuated
Tab. 7: Display elements AS-Interface
4)
Color setting ex works. Can be set via jumper (see “Fig. 18”).
english
Type 8691