11.2 Maintenance work

11.2.1 actuator

The actuator of the diaphragm control valve is maintenance-free
provided it is used according to these operating instructions.

11.2.2 Wearing parts of the diaphragm

control valve

Parts which are subject to natural wear:
• Seals
• Diaphragm

If leaks occur, replace the particular wearing part with an appro-
priate spare part (see chapter “13 Replacement parts”).

A bulging PTFE diaphragm may reduce the flow.

The replacing of the wearing parts is described in chapter
“12 Repairs”.

11.2.3 inspection intervals

Check diaphragm for wear after maximum 10

5

switching cycles.

Muddy and abrasive media require correspondingly shorter
inspection intervals!

11.2.4 service life of the diaphragm

The service life of the diaphragm depends on the following factors:
• Diaphragm material
• Medium, Medium pressure, Medium temperature
• Actuator size
• Pilot pressure for CFB.

protecting the diaphragm

For CFB try and select the pilot pressure not higher than is
required to actuate the medium pressure.

11.2.5 cleaning

Commercially available cleaning agents can be used to clean the
outside.

NoTe!

avoid causing damage with cleaning agents.

▶ Before cleaning, check that the cleaning agents are compatible

with the body materials and seals.

Follow instructions for use in the Ex area!
See chapter “3.1”

.

22

Maintenance,cleaning

english

Type 2730 / 2731 DN 65-100