2702 - 21

C

ommissioning

english

eleCtRICal ConneCtIon - teRMInals foR Cable bUshIng
(toPCONTROL tYPe 8630)

Remove the cover with the cable bushings to gain access

to the screw terminals. This is done by unscrewing the
4 self-tapping screws.

Connection PCb of the toPControl Continuous with screw terminals and
jumpers

terminal configuration with cable bushings

attentIon! For connection to the technical earth (ground) (TE), a threaded stud with nut is provided

on the connection module. To assure electromagnetic compatibility (EMC), connect this
stud to a suitable earthing (grounding) point using as short a cable as possible
(max. 30 cm).

Use of the 4 - 20 mA setpoint input

If the voltage supply of a TOP

Control Continuous device fails in a row of such devices con-

nected in series, the input of the failed device will become high-impedance. This will cause the
4 - 20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.

note

terminal allocation

external connection

1
2

Setpoint +
Setpoint GND

1

2

+ (0/4 ... 20 mA or 0 ... 5/10 V)

GND

3

4

Analog position feedback +

Analog position feedback GND

3

4

+ (0/4 ... 20 mA or 0 ... 5/10 V)
completely isolated electrically
GND

5
6

Operating voltage +
Operating voltage GND

5

6

24 V DC ± 10 %
max. residual ripple 10 %