beautypg.com

Output signals for sps (circular plug m 16), Operating voltage (circular plug m 12) – Burkert Type 2702 User Manual

Page 19

background image

2702 - 19

C

ommissioning

english

operating voltage (circular plug M 12)

Inductive proximity switches (circular socket M8)

output signals for sPs (circular plug M 16)

PIn

allocation

external connection/signal level

A

B

Setpoint GND

Setpoint + (0/4..20 mA or 0..5/10 V)

B

A

+ (0/4...20 mA or 0..5/10 V)
completely isolated electrically
GND

C

D

Analog position feedback +

Analog position feedback GND

C

D

+ (0/4...20 mA or 0...5/10 V)
completely isolated electrically
GND

E

F

G

Binary output 1

Binary output 2

Binary output GND

E

F

G

24 V / 0 V

24 V / 0 V

24 V / 0 V

H

J

Binary input +

Binary input GND

H

J

+

0 ... 5 V (log. 0)

10 ... 30 V (log. 1)

GND

K

L

M

not connected

not connected

not connected

PIn

allocation

external connection

1

2

3

4

+ 24 V

not connected

GND

not connected


1

3

24 V DC ± 10 %
max. residual ripple 10 %

PIn

allocation

signal level


1

2


Proximity switch 1 +(NO)

Proximity switch 1 GND


+24 V DC

GND

S1

1

2


open / 24 V

GND


3

4


Proximity switch 2 +(NO)

Proximity switch 2 GND


+24 V DC

GND

S2

3

4


open / 24 V

GND