Output signals for sps (circular plug m 16), Operating voltage (circular plug m 12) – Burkert Type 2702 User Manual
Page 19
2702 - 19
C
ommissioning
english
operating voltage (circular plug M 12)
Inductive proximity switches (circular socket M8)
output signals for sPs (circular plug M 16)
PIn
allocation
external connection/signal level
A
B
Setpoint GND
Setpoint + (0/4..20 mA or 0..5/10 V)
B
A
+ (0/4...20 mA or 0..5/10 V)
completely isolated electrically
GND
C
D
Analog position feedback +
Analog position feedback GND
C
D
+ (0/4...20 mA or 0...5/10 V)
completely isolated electrically
GND
E
F
G
Binary output 1
Binary output 2
Binary output GND
E
F
G
24 V / 0 V
24 V / 0 V
24 V / 0 V
H
J
Binary input +
Binary input GND
H
J
+
0 ... 5 V (log. 0)
10 ... 30 V (log. 1)
GND
K
L
M
not connected
not connected
not connected
PIn
allocation
external connection
1
2
3
4
+ 24 V
not connected
GND
not connected
1
3
24 V DC ± 10 %
max. residual ripple 10 %
PIn
allocation
signal level
1
2
Proximity switch 1 +(NO)
Proximity switch 1 GND
+24 V DC
GND
S1
1
2
open / 24 V
GND
3
4
Proximity switch 2 +(NO)
Proximity switch 2 GND
+24 V DC
GND
S2
3
4
open / 24 V
GND