English, Process value (circular plug m 8) – Burkert Type 2702 User Manual
Page 20
20 - 2702
C
ommissioning
english
* May be set via software
(section Procedure for specifying the basic settings)
** The jumper is situated on the connection board of the TOPControl Continuous (see next
page)
Process value (circular plug M 8)
For line compensation reasons, connect sensor Pt-100 via 3 conductors. PIN 3 and PIN 4 must
be bridged at the sensor.
note
Input type *
PIn
allocation
Jumper ** external connection
4 ... 20 mA
- internal
supply
1
2
3
4
+ 24 V supply transmitter
Output transmitter
GND
bridge to GND
4 ... 20 mA
- external
supply
1
2
3
4
not connected
Process actual +
not connected
Process actual -
2
4
4 ... 20 mA
GND
Frequency
- internal
supply
1
2
3
4
+ 24 V - supply sensor
Clock input +
Clock input - (GND)
not connected
1
2
3
+24 V
Clock +
Clock -
Frequency
- external
supply
1
2
3
4
not connected
Clock input +
Clock input -
not connected
2
3
Clock +
Clock -
Pt-100
(see note
below)
1
2
3
4
not connected
process actual 1 (current supply)
process actual 3 (GND)
process actual 2 (compensation)
2
3
4
Pt 100