beautypg.com

English, Process value (circular plug m 8) – Burkert Type 2702 User Manual

Page 20

background image

20 - 2702

C

ommissioning

english

* May be set via software

(section Procedure for specifying the basic settings)

** The jumper is situated on the connection board of the TOPControl Continuous (see next
page)

Process value (circular plug M 8)

For line compensation reasons, connect sensor Pt-100 via 3 conductors. PIN 3 and PIN 4 must
be bridged at the sensor.

note

Input type *

PIn

allocation

Jumper ** external connection

4 ... 20 mA
- internal
supply

1
2
3
4

+ 24 V supply transmitter
Output transmitter
GND
bridge to GND

4 ... 20 mA
- external
supply

1
2
3
4

not connected
Process actual +
not connected
Process actual -

2

4

4 ... 20 mA

GND

Frequency
- internal
supply

1
2
3
4

+ 24 V - supply sensor
Clock input +
Clock input - (GND)
not connected

1

2

3

+24 V

Clock +

Clock -

Frequency
- external
supply

1
2
3
4

not connected
Clock input +
Clock input -
not connected

2

3

Clock +

Clock -

Pt-100
(see note
below)

1
2
3
4

not connected
process actual 1 (current supply)
process actual 3 (GND)
process actual 2 (compensation)

2

3

4



Pt 100