beautypg.com

English, Installation of the valve, Procedure for top control type 8630 – Burkert Type 2702 User Manual

Page 14

background image

14 - 2702

C

ommissioning

english

1. Remove the electrical and pneumatic supplies from the Top

Control.

2. Pull off the pneumatic hose between Top

Control and actuator at

control connection of actuator.

3. Control function A:

Pressurize the lower pilot air port of the actuator with compressed air
(6 bar),
so that the plug is lifted from the valve seat and is not damaged.

Control function B:

With control function B, no compressed air must beapplied for this
purpose.

4. Remove the actuator in the open valve position by unscrewing the

nipple from the valve body.

5. Before reinstalling the actuator (in the open valve position), grease the

nipple thread with stainless steel lubricant,
e. g. Klüberpaste UH1 96-402 from company Klüber.

6. Replace the graphite seal.

7. After tightening the threaded nipple, align the pilot air ports by turning

the actuator.

InstallatIon of the valve

note

When using in an aggressive environment, you are advised to connect pneumatic hoses to all
free control connections and place their other ends in a neutral atmosphere.

threaded
nipple

May be installed in any position, but preferably with the actuator above.

Observe the flow direction - general rule for control valves: flow direction: Below seat

Clean the piping of contamination!

Before connecting the valve body, take care that piping is aligned!

In the case of weld-end bodies, be sure to remove the actuator before welding.

attentIon!

The valve must be for this in the opened position.

topControl

actuator

valve body

lower
pilot air
port

CaUtIon!

Use of the incorrect lubricant causes contamination!
For special applications such as for oxygen and analysis, use only the approved lubricants.

Procedure for topControl type 8630