Section 2 Installation

2-7

Installation and Operation Manual

X-CM-QmB-eng
Part Number: 541B029AAG
June, 2011

QmB Series IP40, IP66, IP66XP

Power Supply (Pin 5 and Pin 9)

Both Mass Flow Meter and Controller models are connected via Pins 5
(+14 to +27 Vdc) and 9 (power supply common) on the customer
connector. See Section 5, Functional Specifications for current
requirement.

Valve Override (Pin 12; Controller models only)

To open or close the control valve independently of the setpoint signal
(e.g. for process reasons), Pin 12 is available to carry a valve override
signal. Leave floating (i.e. not connected) to allow for normal control
operation. Input impedence on Pin 12 is >50K ohms.

>5 Vdc @ Valve Open
0 Vdc @ Valve Closed

Density or Temperature Output (Pin 13 and Pin 10)

Pin 13 indicates the density or temperature, represented by a 4-20 mA
or 0-5 Vdc signal, proportional to density or temperature. The current
and voltage signals are returned via Pin 10. Maximum series resistance
on Pin 3 is 500 ohms when configured for 4-20 mA. Recommended load
on Pin 13 is >100K ohms when configured for 0-5 Vdc. Do not apply
power to Pin 13.

Alarm Output (Pin 3 and Pin 9)

Pin 3 indicates an alarm condition as an open drain FET configuration.
Maximum voltage is 30 Vdc, maximum current is 100 mA.
(See Figure 2-6 on page 2-8.)

PIN NO.

FUNCTION

Controller

Meter

1

Setpoint Common

N/A

2

0 - 5 Vdc Flow Signal Output

3

Alarm Output

4

*4 - 20 mA Flow Signal Output

5

+14 Vdc to +27 Vdc Power Supply

6

not used

7

*4 - 20 mA Setpoint Input

N/A

8

0 - 5 Vdc Setpoint Input

N/A

9

Power Supply Common

10

Signal Output Common

11

+5 Vdc Reference Output

12

Valve Override Input

N/A

13

*4 - 20 mA or 0 - 5 Vdc Density or Temperature

14

not used

15

not used

Table 2-1 Electrical Interfacing for Quantim

* Do not apply power to these Pins.