Warning, Installation and operation manual – Brooks Instrument QMBM User Manual
Page 21
QmB Series IP40, IP66, IP66XP
Section 1 Introduction
1-9
Installation and Operation Manual
X-CM-QmB-eng
Part Number: 541B029AAG
June, 2011
Certifications and Approvals
Europe - KEMA 05ATEX1068 X
II 3 G EEx nA II T4
II 3 D T 135 C
Per EN 60079-15: 2003, EN 50281-1-1: 1998 + A1
Ambient Temperature: 0
o
C to 65
o
C
Enclosure: IP66
IP66XP Series Explosion-proof/ Flame-proof
United States and Canada- UL Recognized E73889, Vol. 1, Sect. 21.
Explosion-proof , Class I, Division 1, Groups C and D;
Dust Ignition-proof, Class II, Division 1 Groups E, F, and G;
Suitable for Class III, Division 1; T4
Per ANSI/UL 1203 and CSA 22.2 No. 30
Ex nC IIC T4
Per CSA E79-1
Class I, Zone 2, AEx nC IIC T4
Per UL 60079-1
Ambient Temperature: 0
o
C to 65
o
C
Enclosure: Type 4X/ IP66
Europe - KEMA 05ATEX2052X
Ex d IIB T6 / Ex tD A21 IP66 T85
o
C, per EN 60079-0:2006, EN 60079-1:2007
EN 61241-0:2006 and EN 61241-1:2004
IECex-KEM 09,0007X, Ex d IIB T6, Ex tD A21 IP66 T85
o
C, per IEC60079-0:2006,
EN 60079-1:2007, IEC 61241-1:2004, Ambient temperature 0
o
deg. C to +65
o
deg. C
(pending).
Ex d certified cable glands, blind plugs and conduit seals shall be used. A conduit seal shall
be installed immediately at the emclosure wall. Use wiring/cables suitable for at least 80
o
deg. C
NOTE: Ex d slits on the breather drain valve acc. to IECEx TSA 07.0053 U
WARNING
!
Do not open when an explosive atmosphere may be present.
Environmental effects
EMC effects:
The Brooks Quantim series meets the requirements of the EMC
directive 89/336EEC per EN 50081-2 and EN 61326-1. To meet
these specifications, the Brooks Quantim device must be directly
connected to a low impedance (less than 1 Ohm) earth ground.
Signals must use a standard twisted-pair, shielded instrument wire.
Pressure effects:
The Brooks Quantim series meets the requirements of the
Pressure Equipment Directive 97/23/EC. The unit falls into the
category "Sound Equipment Practice".