• Check that ALL “EMERGENCY STOP” (E-Stop) buttons are disengaged (out).

• Check fuse 10’s blown fuse indicator.

• Check wiring; refer to ADS-464 Main Panel Wiring Diagram.

• Retest.

7 “DRUM FAULT” Message

PLC (PROGRAMMABLE LOGIC CONTROLLER) MESSAGE “DRUM FAULT”

a. PROBABLE CAUSE;

1) Stop motion detector module or sensor. With control voltage “ON” (“green” push-button), use the

pendant control in “LOAD POSITION” to rotate the tumbler (basket).

Note input #0, 10 on the PLC, stop the tumbler (basket) and wait for device’s latched relay to de-

energize. The time from when the tumbler (basket) stopped to the relay de-energizing should be

15-20 seconds.

• If the de-energizing time is satisfactory, the unit is operating correctly:

• Check circuit wiring, and Retest (refer to ADS-464 Main Panel Wiring Diagram).

• If the de-energizing time is incorrect:

• Adjust the “time adjust” on the stop motion detector module and retest.

• If the input # 0, 10 on the PLC is not on after several rotations of the tumbler (basket):

• Check fuse 2 and replace if necessary.

• Rotate the tumbler (basket) using the pendant control in “LOAD POSITION.” Does the module’s

L.E.D. (light emitting diode) respond?

• If “YES,” adjust the “sense time” until the L.E.D. (light emitting diode) stays on for 15-20

seconds after tumbler (basket) stops, then refer to section 1 above

• If “NO,” check:

• Inductive proximity sensor for damage.

• Sensor distance from targets is 3/16’. The proximity sensor is located in the same area as

the tumbler (basket) junction box.

• Inductive proximity adjustment.

• Tumbler target.

• Stop motion detector module.