American Dryer Corp. ADS-464 II User Manual

Page 49

background image

45

• If RTD (Resistive Temperature Device) probe is defective, replace the probe.

NOTE: If ALL systems check out fine, call the ADC Service Department at (508) 678-9000.

2. No Control Power (“Blue” Light Off)

a. PROBABLE CAUSES;

1) Line voltage from main fuse disconnected.

2) Main disconnect on the dryer is turned off.

3) OL11 (overload #11) tripped.

4) Fuse #1 is blown.

b. POSSIBLE SOLUTIONS;

1) Verify main line voltage to dryer

• If line voltage is present go to paragraph #2 below.

• If line voltage is not present check fuse disconnected and retest.

2) Attempt to turn the dryer main power handle to the “ON” position

• If the switch does not engage, verify that sprinkler power is “ON” (“red” light on main door).

• If “NO,” refer to paragraph #1 above.

3) Open main enclosure and verify that OL11 has not tripped

• If “YES,” check circuit, restart and test.

• If “NO,” go to section #3 on page 46.

• Verify that fuse #1 has not blown, check that the “RED” L.E.D. (light emitting diode) indicator

is off.

• If “ON” (fuse block L.E.D. “ON”), check circuit, replace fuse and test.