The following information will first describe the sprinkler circuit components and then provide a circuit description.
Please refer to the ADS-464 ladder diagram (which is supplied with the machine) as the following is described.
SPRINKLER CIRCUIT COMPONENTS
OL12 (overload #12) is a 1.6-amp magnetic and thermal overload device set 1-amp. Its function is to
protect and the line voltage of the sprinkler circuit.
T1 is a control transformer whose primary depends on the system line voltage (i.e., 208 VAC, 240 VAC, 380
VAC, 416 VAC, and 480 VAC). Refer to systems nameplate. Its secondary is 110 volts AC.
L3 is a RED indicator installed on the electrical enclosure door. Its function is to indicate the presence of
110 VAC to the sprinkler system.
Sprinkler High Limit Controller (SHLC) - Its function is to monitor a preset hi-limit temperature (which is
currently set to 550º F [287.8º C]) and to control the activation of
the WATER SPRINKLER circuit.
SHLCs (Sprinkler High Limit Controllers) temperature information is derived from the RTD #4 (Resistive
Temperature Device #4), a resistive sensor located on the top right hand side of the tumbler (basket)
section. Its exact location is in proximity of the intake and hi-limit temperature probe.
IMPORTANT: An open RTD (Resistive Temperature Device) probe or disconnecting the probe under
power will cause the sprinkler to active.
ALL ADS-464 RTD (Resistive Temperature Device) probes are rated for 1,100º F (593.3º C).
SHCL #2 (Sprinkler High Limit Controller #2) contacts (alarm and set point) are configured in the normally
open state.
#2CR (#2 control relay) and #3CR (#3 control relay) are relay coils that are energized in a logical manner
for circuit control. The following are their associated relay contacts information.
S11 and S12 are the actual electrical solenoid connections that turn on or shut off the air actuated water
valve. The electrical connections for S11 and S12 are located in the solenoid junction box in the burner
section of the dryer.
S11 = Sprinkler ON
S12 = Sprinkler OFF
IMPORTANT: For proper sprinkler and dryer operation, sprinkler must be powered by a separate
or dedicated single-phase (1ø) multi-wire branch circuit at dryers nameplate voltage.