L4 (light #4) is an amber light associated with PB #10 (push button #10), the SPRINKLER RESET
button. These items are located on the electrical enclosures front panel. L4s function is to give a visual
indication that the sprinkler function is asserted and that the pneumatically activated water valve is open.
The air actuated water valve also has a visual indicator to show its current state. Notice a RED button on
the rear side of the valve.
IN = Valve CLOSED
OUT = Valve OPEN
NOTE: The sprinkler water inlet line has a hand operated gate valve and must be open for water to
flow. It is suggested that this manual valve be closed when working on the dryer, to avoid
problems caused by false tripping of the sprinkler circuit.
IMPORTANT: BE SURE TO TURN ON THE VALVE WHEN THE WORK IS COMPLETE.
PB #10 (push button #10) SPRINKLER RESET button is for resetting the sprinkler circuit once the
temperature in the tumbler (basket) has dropped below its preset trip temperature.
NOTE: Pressing the SPRINKLER RESET button before the tumbler (basket) temperature has
dropped below its trip temperature will momentarily stop the water flow. However, the water
flow will resume once the button is released.
UV is the UNDER VOLTAGE detection coil of the ADS-464 MAIN DISCONNECT switch, DISC #1.
It is this device that controls the automatic POWER DOWN of the dryer when the sprinkler is activated.
SPRINKLER CIRCUIT DESCRIPTION
The following information assumes that the reader has read the sprinkler component descriptions and is following
the ADS-464 Ladder Diagram of the Sprinkler Circuit.
STATE 1 - The tumbler (basket) temperature is BELOW SHLC (Sprinkler High Limit Controller) preset
trip value. When power is applied to SHLC:
SHLC set point will close.
SHLC alarm will open.
UV (under voltage) will engage.