beautypg.com

American Dryer Corp. ADS-464 II User Manual

Page 23

background image

19

3. Steam Supply and Condensate Return Connections

The steam supply into the dryer is made into the 2-1/2” F.T.P. pipe fitting located on top of the heat module

console.

The maximum operating steam supply pressure is 150 psig (1,034 kPa).

The presence of condensate in the steam supply will cause water hammer and subsequent steam coil

(battery) failure. The steam supply connection out of the main supply line must be made with a minimum

10-inch (25.4 cm) riser. This will reduce the amount of condensate in the steam supply.

Use flexible couplings at the supply and return connections. The dryer vibrates slightly when it runs and the

piping connections may crack if they are hard piped to the dryer. Install shut-off valves in the supply and

return lines.

An inverted bucket steam trap with an internal check valve is included with the dryer. The supply lines

should be insulated. This will save energy and provide for the safety of the operator and maintenance

personnel.

Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing

steam coil damage. ALL horizontal runs of steam supply piping should be pitched 1/4-inch (0.08 cm) for

the header. Install a bypass trap in any low point to eliminate wet steam.

The condensate return line must be 1-1/4” pipe.