beautypg.com

Bray 70 Series SERVO PRO User Manual

Page 12

background image

10

BRAY Series 70 Servo Pro

Operation and Maintenance Manual

Transient Suppression
Electromagnetic Interference (EMI) can result from

inductive loads, which can adversely affect electronic

circuits.

Appropriately sized surge suppressors should

be installed whenever inductive loads such as

transformers, relays, solenoids, motors, etc. are

operated. This will help prevent transient EMI surges

from damaging the sensitive electronic circuits.

H. Apply the appropriate supply voltage to the power

input terminals.

a. Verify the Status LED is flashing normal operation

– a green “heartbeat” consisting of a repeating

pattern one second on and one second off.

b. If the Status LED is flashing red, the problem must

be resolved before Calibration can begin. Refer

to the Troubleshooting section of this manual and

the Status Code Flash Table for more information.

I. Accept or Adjust the Deadband - Optional

a. The factory default is midrange – the deadband

potentiometer is midway between fully clockwise

and fully counter-clockwise. If this is acceptable,

no further adjustment is necessary.

b. Rotate the deadband potentiometer clockwise to

increase the deadband.

c. Increasing the deadband reduces the potential

for the actuator to oscillate around the desired

setpoint. This oscillation is often called “hunting.”

An actuator responding to a moving setpoint is

not hunting, but is operating properly.

d. Decreasing the deadband allows the actuator to

reach a position closer to the desired position,

as long as the actuator does not oscillate (hunt)

around the setpoint.

J. Accept or Adjust the Open Speed - Optional

a. The factory default is full speed – the open speed

potentiometer is in the fully counter-clockwise

position. If this is acceptable, no further adjustment

is necessary.

b. The full speed (fastest speed) of the actuator is

listed on the label.

c. Rotate the open speed potentiometer clockwise

to reduce the opening speed of the actuator.

d. Reducing the opening speed of the actuator can

allow more precise positioning of the actuator.

K. Accept or Adjust the Close Speed - Optional

a. The factory default is full speed – the close speed

potentiometer is in the fully counter-clockwise

position. If this is acceptable, no further adjustment

is necessary.

b. The full speed (fastest speed) of the actuator is

listed on the label.

c. Rotate the close speed potentiometer clockwise

to reduce the closing speed of the actuator.

d. Reducing the closing speed of the actuator can

allow more precise positioning of the actuator.

notice

Reducing the closing speed of the actuator can also

reduce the potential of water hammer damage. Electric

actuators are usually slow enough to avoid water

hammer even at the full speed setting – but the user

should verify this setting.

Shielding
Signal/communication lines should be shielded.

Shield must be grounded at one end only, preferably

at the controller. Grounding the shield at more than

one location can introduce noise in the circuitry by

forming ground loops.

L. Connect the Output Signal to the process controller

- Optional

a. Wire the positive conductor to the OUTPUT (+)

terminal.

b. Wire the negative conductor to the OUTPUT (-)

terminal.

c. Select the desired output signal range using the

Configuration switches 4, 5 and 6.

M. Connect the Anti-Condensation Heater – Optional

a. Connect the wires from the Anti-Condensation

Heater to the HEATER terminals

b. The Heater rating must match the voltage rating

of the Servo Pro