beautypg.com

Bray 70 Series SERVO PRO User Manual

Page 11

background image

9

BRAY Series 70 Servo Pro

Operation and Maintenance Manual

E. Verify (or adjust) the travel stop limits in the actuator

a. Bray actuators are shipped with the travel switches

in the factory default position - close travel limit

set at 0 degrees and the open travel limit set at

90 degrees

b. Bray actuators equipped with Servo Pro have

the internal feedback potentiometer set in the

proper position to match the travel switch factory

default (fully close at 0 degrees and fully open at

90 degrees)

c. If the travel switch settings are moved from the

factory default position, the internal feedback

potentiometer must be adjusted to match the new

travel switch setting. This is done by performing

a calibration routine.

d. For more details on setting the travel switch

settings, refer to the S70 Operation and

Maintenance Manual.

F. Select the Torque Switch Enable or Disable

a. If optional torque switches are installed in the

actuator, select Torque Switch Enable. The

optional torque switches must be properly set and

wired to the Servo Pro. Refer to the S70 Operation

and Maintenance Manual for more information.

b. If optional torque switches are not installed in the

actuator, select Torque Switch Disable.

Warning

Before applying the appropriate electrical supply

voltage, verify that the actuator and Servo Pro have been

properly wired to the factory supplied wiring diagram.

NOTICE

To prevent noise coupling between conductors, power

lines and signal/communication lines should not be

routed together in the same conduit or cable tray. If

they must cross each other, then it should only be done

at right angles

Recommended distances below should be maintained

between power and signal/communication conduit:

Metal Conduit:

Conductor carrying less than 20A = At least 4 in.

Conductor carrying more than 20A up to 100kVA = At

least 8 in.

Conductor carrying more than 100kVA =At least 1.5 ft

Non-Metallic Conduit:

Conductor carrying less than 20A = At least 8 in

Conductor carrying more than 20A up to 100kVA = At

least 2 ft

Conductor carrying more than 100kVA = At least 3 ft.

Please refer to NEC guidelines for proper wiring

techniques in USA. Other countries must follow all local

codes for safety requirements.

Shielding
Signal/communication lines should be shielded. Shield

must be grounded at one end only, preferably at the

controller. Grounding the shield at more than one location

can introduce noise in the circuitry by forming ground

loops.

G. Apply the command signal input

notice

Ensure that your controller is able to provide the

proper command signal range given the following

input impedance values:

4-20 mA

200 Ohm

0-5 VDC

>10 MOhm

0-10 VDC

>10 MOhm

a. The command signal must be connected to the

proper terminals. Refer to the wiring diagram.

b. The command signal input must match the range

selected with the configuration switches.

c. The command signal must be a valid value (i.e.,

if 4-20 mA DC is selected, the value must be no

less than 4 mA and no greater than 20 mA.)

d. Note: a good value to select for Calibration would

be mid-travel (i.e. 12 mA DC)

Isolation Transformers

For circuits that are located in the proximity of

excessive electrical noise generators, isolation

transformers should be used to filter and prevent

noise from entering into the circuitry.

!