AVTECH Room Alert 3E Monitor (RA3E-ES0-BAS) User Manual
Page 26

Room Alert 3E
22
AVTECH Software, Inc.
3. Enter values in the “High” and “Low” field to set high and low thresholds. Your Room
Alert 3E will send an alert email or email-to-SMS in response to these temperatures.
4. Enter a value in the “Adjust” field to calibrate your digital sensor if its reading differs
from a known value at that location.
5. Click
Accept Changes
at the bottom of your screen.
6. Click
Save Settings
in the navigation bar to the left of your screen.
Sensor 3 Alarm Configuration (External Switch Sensor)
You may configure the alert state for an external switch sensor in the “Sensor 3 Alarm
Configuration” fields.
Your Room Alert 3E monitors your switch sensor for “Open” or “Closed” status. After you
connect your switch sensor—and before you configure it—determine whether its normal state is
“Open” or “Closed” by looking at the “Status” page of the web interface:
1. Click the
Status
tab at the top of your screen in the web interface.
2. Look at the current status of “Channel 3: Switch Sensor.” It should show the normal
sensor state, which is “Open” or “Closed.” This example shows normal state as “Closed.”
TIP
The options in these fields vary slightly depending on the type of
digital sensor you connect. Notice, for example, that the Digital
Temperature & Humidity Sensor has a “Monitor Heat Index” option.