AVTECH Room Alert 3E Monitor (RA3E-ES0-BAS) User Manual
Page 22

Room Alert 3E
18
AVTECH Software, Inc.
SNMP Configuration
To begin configuring your Room Alert 3E for SNMP:
1. In “Community Name,” you may leave the default SNMP protocol community name—
“public”—or enter a new name.
2. You may leave “Contact (sysContact)” blank or enter a person’s name to specify who is
receiving the information.
3. You may leave “Location (sysLocation)” blank or enter the location of your Room Alert
3E monitor.
4. You may click
Use 2 digit SNMP
if you prefer to receive values in 2-digit rather than
4-digit format.
5. Click
Accept Changes
at the bottom of your screen.
6. Click
Save Settings
in the navigation bar to the left of your screen.
TIP
Room Alert 3E sends values to your 3
rd
-party SNMP monitoring
application in 4-digit format by default. 78.55° F, for example,
appears as 7855. In 2-digit format, your values are truncated,
not rounded to the nearest number. In this example, 78.55
would appear as 78.
TIP
The community name you assign here must match the one in
your 3
rd
-party SNMP monitoring application.