AVTECH Room Alert 3E Monitor (RA3E-ES0-BAS) User Manual
Page 25

Room Alert 3E
AVTECH Software, Inc.
21
3. Enter values in the “High” and “Low” field to set high and low temperature thresholds.
4. Enter a value in the “Adjust” field to calibrate the Internal Temperature Sensor if its
reading differs from a known temperature value at that location.
5. Click
Accept Changes
at the bottom of your screen.
6. Click
Save Settings
in the navigation bar to the left of your screen.
Sensor 2 Alarm Configuration (External Digital Sensor)
You may configure alert thresholds for an external digital sensor in the “Sensor 2 Alarm
Configuration” fields.
In this example, we’ll configure an external Digital Temperature & Humidity Sensor:
1. In “Sensor Label,” you may leave the default label, “Sensor 2,” or rename it to
something more descriptive, such as “Temp & Humidity.”
2. The “Alarm On” fields automatically match the type of sensor you connect. In this
example, the “Alarm On” settings are Temperature and Humidity.
Refer to the
Advanced
section in this manual for instructions on
setting the default temperature scale.
NOTE
The digital port also takes a Light Tower & Relay Adapter;
however, you do not configure Light Tower or Relay options
here—refer instead to the
Alarm Options
section in this manual.
NOTE