3.0 Enclosure Options

3.1 Battery Remote Temperature Sensor (RTS)

Procedure:

1. Attach the RTS probe to the inner side of battery 2A with adhesive tape.

2. The other side of the RTS probe is attached to the front panel of the XM2 power supply,

in the jack labeled TEMP PROBE.

Fig. 3-1, RTS Placement

For enclosures with multiple battery strings, the Remote Temp Sensor (RTS) must be located with
the warmest (normally the topmost) battery string. This ensures proper operation of the battery
charger’s temperature compensation circuit. Failure to locate the RTS with the warmest battery
string could result in overcharging and premature battery failure.

CAUTION!