8 power supply placement, 9 battery installation – Alpha Technologies UPE-6 User Manual
Page 23

23
031-124-C0-004, Rev. D
2.0 Installation,
continued
2.8 Power Supply Placement
Place the power supply on the top shelf over the vent louvers on the right. Do not connect
any cables or connectors to the power supply at this time.
2.9 Battery
Installation
Battery systems represent a risk of electrical shock and high short-circuit currents. The
following precautions must be observed when maintaining batteries:
•
Remove all personal metal objects (watches, rings, etc.)
•
Use insulated tools
•
Wear eye protection and rubber gloves
•
Observe circuit polarities
•
Do not make or break live circuits
•
Do not lay metal tools and hardware on top of the batteries
WARNING!
2.9.1 Battery Date Code Usage and Identifi cation
Every battery contains a DATE CODE. This code is usually located near the positive
(+) terminal, and must be recorded in the maintenance log. If you use batteries other
than those installed by Alpha, consult the batteries’ manufacturer’s documentation for
date code type and placement.
The date code scheme and location varies depending on the age of the battery used.
NOTE:
Month: June
Year: 2005
Fig. 2-5, Battery Date Code