3 system status indicators and reset button, 1 detailed led descriptions, Fig. 9-4, led functionality and indications – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual
Page 83: 0 start up and verification

83
745-814-B11-001, Rev. C (03/2014)
Fig. 9-4, LED Functionality and Indications
9.3
System Status Indicators and Reset Button
As viewed from the front of the unit, the DSM3 Series utilizes LEDs to indicate system status. During
system start up, the LEDs will first blink momentarily then indicate the current status of a variety of
parameters on the DSM3 Series Communications Module. The LEDs indicate alarms, RF power level
status, battery string connectivity and communications activity with the network. A description of each LED
follows.
LED
Status
Behavior
Indication
ALM/RDY: Alarm and Ready
N/A
OFF
No power or malfunctioning Communications Module
GRN
ON
Reset of the DSM3 Series is in process
Steady Blinking
Normal operation
RED
Blinking more OFF than ON
Minor Alarm SCTE-HMS configured
Blinking more ON than OFF
Major Alarm SCTE-HMS configured
REG: Upstream ranging and
registration lock.
GRN
OFF
No power, upstream frequency undetermined
OFF / ON
Power on, downstream locked, upstream frequency ranging,
DHCP request in progress
ON
CMTS registration completed
DS: Downstream RF Carrier
detection and lock.
GRN
OFF
No power / downstream carrier
OFF / ON
Power on, downstream carrier frequency searching
ON
Downstream carrier lock
ACT: CPE Activity status
GRN
OFF
No Ethernet communications activity
OFF/ON
Momentary flash while CPE communications ongoing via
the Ethernet craft port
LNK: CPE Link status
GRN
OFF
No Ethernet link
ON
Link on Ethernet Craft port
RF Rx/Tx Power Level Indicator
TRI
OFF
No RF detected
Blue
Rx/Tx Power at a warning level as set within the
SCTE-HMS Property Table
Green
Rx/Tx RF Power level within tolerance
Red
Rx/Tx Power at an alert level as set within the
SCTE-HMS Property Table
COM: AlphaBus
communications.
GRN
OFF
No AlphaBus Communications
OFF/ON
Momentary flashes - AlphaBus Port communications
active
BATT A/B
GRN
ON/OFF
ON (steady) if battery string(s) connected correctly
BATT C/D
GRN
ON/OFF
ON (steady) if battery string(s) connected correctly
ALM/RDY
REG
ACT
LNK
RF
BATT A/B
BATT C/D
COM
9.0 Start Up and Verification
9.3.1 Detailed LED Descriptions
After power is applied or a reset occurs, all LEDs will flash in certain patterns indicating the cable
modem chipset is starting or restarting. Once it is ready, it will begin the DOCSIS requirement of
searching for the downstream frequency lock and the LEDs will follow the detailed descriptions
below.
ALM/RDY - Alarm/Ready
The ALM/RDY - During normal operation, this LED blinks GREEN, indicating a heartbeat pulse
from the processor. The frequency of flashing by this LED provides a visual alert for power supply
discrete major and minor alarms, if configured in the property and discrete property tables of the
SCTE-HMS MIB. The ALM LED (RED) is factory defaulted OFF. Refer to
Section 6.2.3, General
Power Supply Alarms for information on configuring the DSM3 Series for active monitoring and
alarming. If an event triggers an HMS alarm, the ALM/RDY LED blinks RED according to the
alarm type until the alarm has been resolved. For a minor alarm, the frequency of flashing (RED)
will be more OFF than ON and for a major alarm the frequency of flashing will be (RED) more
ON than OFF. If there are multiple active alarms, including one or more major alarms with one or
more minor alarms, the major alarm will take precedence in terms of the indication.
DS