0 data management, 3 general power supply alarms – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual
Page 59

59
745-814-B11-001, Rev. C (03/2014)
6.2.3 General Power Supply Alarms
6.0 Data Management
Table 6-8, Power Alarms: Classifications, Causes and Corrections
Active Alarm
Alarm type
Alarm Category
Probable Cause of Alarm
Corrective action
Standby Disabled
Self Test FAIL
Major
PWR
Output voltage failed or batteries less than 1.85V/C during
Self Test.
1. Check Batteries
2. Check Inverter
NO
LINE ISOLATION
Major
PWR
Line isolation has failed and Inverter operations are
suspended.
1. Replace Power Supply as soon as
possible
YES
OUTPUT FAILURE
Major
PWR
The AC output has failed due to a bad Inverter or
transformer.
1. Apply load >1.5A
2. Output Overloaded
3. Check Inverter
NO
OUTPUT OVERLOAD
Major
PWR
The output is overloaded or shorted.
1. Output Short Circuit
2. Check Output Current
NO
OUTPUT 1 TRIPPED
Major
PWR
Output 1 AlphaDOC hardware protection mode is engaged
and overloaded.
1. Over Current
2. Check Settings
NO
OUTPUT 2 TRIPPED
Major
PWR
Output 2 AlphaDOC hardware protection mode is engaged
and overloaded.
1. Over Current
2. Check Settings
NO
CHARGER FAILURE
Major
PWR
Charger has failed to shut down; possible battery over
temperature condition exists.
1. Re-seat Inverter
2. Perform Self Test
NO
INVERTER TEMP
Major
PWR
Inverter heat sink has exceeded set temperature. (Stand-
by operations suspended until temperature drops to a
safe level.)
1. Check Inverter
2. Check PDB
3. Check Enclosure Ventilation
NO
CONFIG ERROR
Major
PWR
The Power Supply is improperly configured and
operation is suspended until error is corrected.
1. Wrong Input Voltage or Frequency
NO
INVERTER ALARM/
INVERTER FAILED
Major
PWR
No output detected with good batteries for 30 seconds
OR inverter is disconnected from PDB.
1. Re-seat Inverter
2. Replace Inverter
YES
INPUT FAILURE
Minor
PWR
Utility AC input has failed.
1. Utility Failure
2. Check Input Breaker
3. Input Connections
NO
INPUT OVER CURR /
INPUT CURRENT LIMIT
Minor
PWR
AC Input current exceeds threshold setting.
1. Reduce Output Load
2. Check Input Current Limit Setting
NO
SURGE MOV FAIL
Minor
PWR
The MOV board surge protection has failed and needs
to be replaced.
1. Replace MOV Board
NO
ALPHADOC OPTION
Minor
PWR
I2C has failed between XM3 and DOC.
1. Check Ribbon Cable
2.Replace DOC
NO
INVERTER ENABLE
Minor
PWR
System controller has disabled the Inverter.
1. Check Inverter
YES
CHARGER ENABLE
Minor
PWR
System controller has disabled the charger.
1. Check Charger
NO
APP OPTION
Minor
PWR
I2C has failed between XM3 and APP.
1. Check Ribbon Cable
2. Replace APP
NO
INV EEPROM ERROR
Minor
PWR
There has been an error reading the EEProm on the
inverter board.
1. Replace Inverter
NO
HW COMPATIBILITY
Minor
PWR
There is a hardware incompatiblity between the main
micro board and the inverter board.
1.Check Micro Board
2.Check Inverter Brd
NO
PDB EEPROM ERROR
Minor
PWR
There has been an error reading the EEProm on the
PDB.
1.Replace Power Supply
NO