4 dsm3 leds and connections, Fig. 7-5, dsm3 leds and connectors, 0 installation – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual
Page 68

68
745-814-B11-001, Rev. C (03/2014)
Item LED or Connector
Status
Behavior
Indication
1
ALM/RDY: Alarm and
Ready
N/A
OFF
No power or malfunctioning Communications
Module
GRN
ON
Communications Module reset in process
Steady Blinking Normal operation
RED
Blinking more
OFF than ON
Minor Alarm
Blinking more
ON than OFF
Major Alarm
2
REG: Upstream
ranging and
registration lock
GRN
OFF
No power, upstream frequency undetermined
BLINKING
Power on, downstream locked, upstream
frequency ranging, DHCP request in progress
ON
CMTS registration completed
3
DS: Downstream RF
Carrier detection and
lock
GRN
OFF
No power / downstream carrier
BLINKING
Power on, downstream carrier frequency searching
ON
Downstream carrier lock
4
ACT: CPE Activity
status
GRN
OFF
No Ethernet communications activity
BLINKING
Momentary flashes during CPE communications
via the Ethernet Craft port
5
LNK: CPE Link status
GRN
OFF
No Ethernet link
ON
Link on Ethernet Craft port
6
RF Rx/Tx Power Level
Indicator
TRI
OFF
No RF detected
Blue
Rx/Tx Power at a warning level as set within the
SCTE-HMS Property Table
Green
Rx/Tx RF Power level within tolerance
Red
Rx/Tx Power at an alert level as set within the
SCTE-HMS Property Table
7
BAT A/B
GRN
ON/OFF
ON (steady) if battery string(s) connected correctly.
8
BAT A/B Connector
9
RST: Reset Buttton
10
TPR: Tamper Switch Connector
11
ETH: Ethernet Connection
12
RF Connection
13
CM, CPE MAC Address Label
Fig. 7-5, DSM3 LEDs and Connectors
7.4
DSM3 LEDs and Connections
7.0 Installation
9
10
11
1
2
3
7
4
5
6
12
13
8