0 data management, 1 scte-hms configurable alarms, continued – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual
Page 53

53
745-814-B11-001, Rev. C (03/2014)
6.0 Data Management
Discrete Alarms
Description
Setting
psInverterStatus (1)
Inverter OFF
Disable
psInverterStatus (2)
Inverter running due to loss of AC Line voltage
discreteMinor
psInverterStatus (3)
Self Test initiated locally
Disable
psInverterStatus (4)
Self Test initiated remotely
Disable
psInverterStatus (5)
Last Self Test failed
Disable
psMajorAlarm (1)
No Alarm
Disable
psMajorAlarm (2)
Alarm
discreteMajor
psMinorAlarm (1)
No Alarm
Disable
psMinorAlarm (2)
Alarm
discreteMinor
psTamper (1)
Closed
Disable
psTamper (2)
Open
discreteMajor
psInputVoltagePresence (1)
AC Line Voltage lost
Disable
psInputVoltagePresence (2)
AC Line Voltage present
Disable
Battery Standby Time Remaining
(1)
Over 3 hours remaining
Disable
Battery Standby Time Remaining
(2)
2 to 3 hours remaining
Disable
Battery Standby Time Remaining
(3)
1 to 2 hours remaining
discreteMinor
Battery Standby Time Remaining
(4)
Less than 1 hour remaining
discreteMajor
Battery Standby Time Remaining
(5)
Calculating
Disable
Battery Standby Time Remaining
(6)
Not Available
Disable
tibControlMode (2)
Device is under local control
Disable
tibControlMode (3)
Remote device is not responding
discreteMajor
Discrete Alarms for Optional Generator
genGeneratorStatus (1)
Generator OFF
Disable
genGeneratorStatus (2)
Generator running (Test)
discreteMinor
genGeneratorStatus (3)
Generator running
discreteMajor
genGeneratorStatus (4)
Generator fail
discreteMajor
genGasHazard (1)
No Alarm
Disable
genGasHazard (2)
The concentration of hydrocarbon fuel in the generator enclosure has exceeded safe limits. Generator
operation is suspended. The alarm is cleared when the sensor reports safe conditions, and the alarm is reset
via the resetLatchedAlarms(3) command found in the genEquipmentControl MIB point.
discreteMajor
genWaterIntrusion (1)
No Alarm
Disable
genWaterIntrusion (2)
Water level within the generator or fuel enclosure has exceeded safe limits for generator operation. Generator
operation is suspended while this alarm is active. The alarm resets when the water returns to a safe level.
discreteMajor
genPadShear (1)
No Alarm
Disable
genPadShear (2)
Indicates that the generator or fuel enclosure has shifted from its mounting position. Generator operation is
suspended. The alarm resets when the unit is returned to its original position.
discreteMajor
genEnclosureDoor (1)
No Alarm
Disable
genEnclosureDoor (2)
Generator and/or auxiliary fuel enclosure door is open
discreteMajor
genCharger (1)
No Alarm
Disable
genCharger (2)
Ignition battery charger is not operating correctly
discreteMajor
genFuel (1)
No Alarm
Disable
genFuel (2)
Indicates the engine's fuel supply is insufficient for extended operation. Alarm resets when fuel is replenished. discreteMajor
genOil (1)
No Alarm
Disable
genOil (2)
Indicates the engine's oil is inadequate for safe operation. Alarm resets when the condition returns to normal.
discreteMajor
genMinorAlarm (1)
No Alarm
Disable
6.2.1 SCTE-HMS Configurable Alarms, continued
Table 6-4, Recommended Settings for Discrete Alarms