8. Test sensor (verify that an alarm is produced at

ATG console), if it does produce an alarm, seal

EYS seal fittings and electrical connectors with

epoxy.

9. Turn off power again if other devices are to be

installed (Repeat Step 3).

Eys seal fitting

1/2 or 3/4 inch

conduit to console

1/2 or 3/4 inch

conduit to console

Weatherproof

Junction box

Compression

fitting (cord grip)

Compression

fitting (cord grip)

TSP-KS

DISPENSER SUMP

TSP-DDS

sensor

EYS

Seal

fitting

Concrete slab

Per NFPA 30

Clean fill material

(Gravel typical)

Weatherproof

Junction box

TSP-KS

(Install kit

for TSP-DTS

sensor)

Submersible

pump

TURBINE SUMP & COVER

TSP-DTS

sensor

(Install kit for

TSP-DDS sensor)

TSP-DDS

TSP-DTS

Figure 2: Sensor Installation

10. Reinstall all safety covers and guards, junction

box gasket and covers – use pipe-dope to seal all

fitting threads.

11. Install the manhole cover.
12. Record the location where the sensor was

installed on the chart on the back page of these

instructions. This information will be needed when

setting up the ATG.

13. Turn on power and program the ATG – Refer to

Sensors in the Setup / Programming & Installation

manuals.

General Installation Notes

It is the installer’s responsibility to

comply with all applicable federal, state

and local codes. Failure to do so may

create an Environmental Hazard.

Plan your conduit routing. Dig trenches as necessary to

install conduit from each junction box to the Intrinsically

Safe (I.S.) knockouts at the ATG console. You must install

a weatherproof, electrical junction box inside each sump.

Access to sumps must be done so all entries are liquid-

proof (to keep product in the sump if a spill or leak occurs).

The junction box should be installed high on the sidewall to

prevent it from being submerged during heavy rains.

Clearance

Holes for

¼-20

Screws

TSP-DDS

or

TSP-DTS

Sensor

J box

Containment sump wall

Weatherproof junction box

EYS seal fitting

Compression

Fitting (cord grip)

Unistrut

Mounting

(Side view)

J box

Mounted against

junction box

(Front view)

The included bracket

allows mounting to a

TSP-KS Unistrut, or to a

vertical surface.

Pipe in sump or

under turbine pump

Figure 3: Mounting Details

A junction box may be used inside of the building and used

as a I.S. pull box to combine several sensor cables. If this

is done, then only one I.S. conduit knockout may be used

at the console. Before pulling wires, mark them to avoid

confusion when connecting to the ATG.

Conduits must have EYS seal fittings

installed in accordance with NFPA

70 (National Electric Code) and NFPA

30A (Automotive and Marine Service

Station Code). Failure to seal conduits

in accordance with NFPA 30A, and

NFPA 70 could allow flammable vapors

to travel through the conduit in the

ATG console. An explosion could result

causing serious injury, property loss,

or death.

Seal all threaded fittings and conduit

threads to produce a weatherproof

seal.