Console — dms sensor wiring connections, Figure 5: sensor connection to console – Franklin Fueling Systems TSP-DMS User Manual
Page 4

©2011 FFS 000-0269 Rev C.
Console — DMS Sensor Wiring Connections
The wiring should connect to the probe module. The probe
module may also have wiring from vapor flow meters
and / or other probes (See Figure 5).
Remove 1-1/2” (38 mm) of jacket from each sensor cable,
and strip off 3/16” (5 mm) of insulation from the end of
each conductor.
In the console, start wiring from channel 1 on probe
module and work up from there. Wire the three wires of
the cable to the PROBE interface terminal set (channel) as
described below:
1) Connect the black wire to the minus – (BLK)
terminal.
2) Connect the red (or yellow) wire to the plus +
(RED) terminal.
3) Connect the cable shield to the same - (BLK)
terminal as the black wire.
Repeat this wiring procedure until all sensors are wired to
the probe input channel terminals (+, – / SHLD). A sensor
or probe can be wired to any input probe channel and will
operate normally after it is setup / programmed correctly.
Probe
Module
RUN
ERR
9
8
7
–Blk
+Red
–Blk
+Red
–Blk
+Red
12
11
10
–Blk
+Red
–Blk
+Red
–Blk
+Red
3
2
1
–Blk
+Red
–Blk
+Red
–Blk
+Red
6
5
4
–Blk
+Red
–Blk
+Red
–Blk
+Red
Vapor Flow Meter
Probe
SHLD
- (BLK)
+ (RED)
SHLD
- (BLK)
+ (RED)
TSP-DMS
SHLD
- (BLK)
+ (RED)
Non-Hazardous
Location
Hazardous Location
Class I, Division 1, Group
D, Group IIA, Zone 0
Figure 5: Sensor Connection to Console