Console — DMS Sensor Wiring Connections

The wiring should connect to the probe module. The probe

module may also have wiring from vapor flow meters

and / or other probes (See Figure 5).
Remove 1-1/2” (38 mm) of jacket from each sensor cable,

and strip off 3/16” (5 mm) of insulation from the end of

each conductor.
In the console, start wiring from channel 1 on probe

module and work up from there. Wire the three wires of

the cable to the PROBE interface terminal set (channel) as

described below:

1) Connect the black wire to the minus – (BLK)

terminal.

2) Connect the red (or yellow) wire to the plus +

(RED) terminal.

3) Connect the cable shield to the same - (BLK)

terminal as the black wire.

Repeat this wiring procedure until all sensors are wired to

the probe input channel terminals (+, – / SHLD). A sensor

or probe can be wired to any input probe channel and will

operate normally after it is setup / programmed correctly.

Probe

Module

RUN

ERR

9

8

7

–Blk

+Red

–Blk

+Red

–Blk

+Red

12

11

10

–Blk

+Red

–Blk

+Red

–Blk

+Red

3

2

1

–Blk

+Red

–Blk

+Red

–Blk

+Red

6

5

4

–Blk

+Red

–Blk

+Red

–Blk

+Red

Vapor Flow Meter

Probe

SHLD

- (BLK)

+ (RED)

SHLD

- (BLK)

+ (RED)

TSP-DMS

SHLD

- (BLK)

+ (RED)

Non-Hazardous

Location

Hazardous Location

Class I, Division 1, Group

D, Group IIA, Zone 0

Figure 5: Sensor Connection to Console