Line Power Wiring

Non-Intrinsically Safe Wiring

Always lock out and tag electrical

circuit breakers while installing or

servicing this equipment and any

related equipment. A potentially

lethal electrical shock hazard and

the possibility of an explosion or fire

from a spark can result if the electrical

circuit breakers are accidentally turned

on during installation or servicing.

Power to the console must be 110 to 240 V~, 50 / 60 Hz.  
At the electrical power panel, use a 20 amp circuit breaker 

used only to supply power to the Colibri console. 
Note: Do not connect other equipment to this circuit. 

Figure 4: Power Wiring Connection

The ground bus in the electrical panel must be

connected to an earth ground as required by the 

National Electrical Code (or Canadian Electrical Code) 

when applicable. If the ground bus is not properly 

connected to an earth ground or if the IS safety ground 

is not properly connected at the console, a dangerous 

condition will be created which could result in an 

explosion. 

Check Electrical Resistance to Earth Ground

After wiring the IS safety grounds, check the resistance 

between the IS safety ground terminals at the console and 

the earth ground – this resistance must be less than 1 ohm.

110/240 VAC Line Power Wire Connection List

Electrical

Panel

No. Conductors, Color

(Gauge)

Circuit

20 Amp Circuit 

Breaker

1 Black wire, 14 AWG (1.6 

mm) min.

110/240 VAC 

Power

Neutral

1 White Wire, 14 AWG (1.6 

mm) min.

Neutral

Ground Bus

1 Green wire, 14 AWG (1.6 

mm) min.

Ground

Ground Bus

1

Green wire, 12 AWG (2.1 

mm) min.

Safety 

Ground

Console Ground Connection

Attach the ground wire to the grounding stud in the 

console.

Nut

Lock Washer

Earth Ground Conductor

Enclosure

Cup Washer

Flat Washer

Figure 5: Ground Stud Connection

Ground Stud

Warning