Leak testing / console operation, Reports – Franklin Fueling Systems TS-STS Sump Test System Kit User Manual
Page 7

Leak Testing /
Console Operation
Continued...
ACK
SHIFT
SELECT SUMP REPORT
TEST
LEVEL
M1
LEFT
M2
RIGHT
M3
M4
J
W
REPORT
9
SELECT SUMP
SUMP 1
SUMP 2
SUMP 3
ALL
M1
LEFT
M2
RIGHT
M3
M4
SELECT ALARM TYPE
SYSTEM
SUMP
ALL
M1
LEFT
M2
RIGHT
M3
M4
SELECT (SYSTEM / SUMP) ALARM STATUS
ACTIVE
CLEARED
HISTORY
M1
LEFT
M2
RIGHT
M3
M4
6.)
To view an alarm/warning,
press
the
M1
or
M2
Key under the
word Alarm / Warning. While viewing the alarm,
press
the
ACK
SHIFT
key at the keypad to acknowledge.
Cleared and
transient alarms should be acknowledged prior to starting
another test.
7.)
Press
the
Report
key at the keypad to show various report
choices.
— ❖ —
Reports
4
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001
12:15 PM
SUMP LEAK TEST REPORT
SUMP 2
TEST STARTED
12:00 PM
TEST STARTED
10/31/01
BEGIN LEVEL
7.0230 IN
END TIME
12:15 PM
END DATE
10/31/01
END LEVEL
7.0209 IN
LEAK THRESHOLD
0.002 IN
TEST RESULT:
FAILED
Reports can printout automatically or on
demand from the keypad. The
Sump Leak Test
and Alarm
Reports print automatically.
The other reports, such as
the Sump Level Reports,
Alarm Reports, and Sump
Test Reports can be printed
on demand.
Press the menu select keys
and choose the type of report
that you wish to printout.
Alarm reports will print as
soon as an alarm is detected.
Leak test reports print
automatically after the leak test is finished.
Note that
when a new leak test is complete the data will
overwrite a previous result.
Of the three reports shown here, one is a Level
Summary report and two are Sump Leak Test
Reports.
Up to 4 sumps can be leak-tested at the same
time.
REPORTS continued...
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001
12:15 PM
SUMP LEAK TEST REPORT
SUMP 1
TEST STARTED
12:00 PM
TEST STARTED
10/31/01
BEGIN LEVEL
2.0120 IN
END TIME
12:15 PM
END DATE
10/31/01
END LEVEL
2.0120 IN
LEAK THRESHOLD
0.002 IN
TEST RESULT:
PASSED
INCON
INTELLIGENT CONTROLS INC.
P.O.. BOX 638
SACO ME 04072
1-800-984-6266
10/31/2001
11:58 AM
SUMP LEVEL REPORT
SUMP 1
2.012 IN
SUMP 2
7.201 IN
SUMP 3
3.218 IN
SELECT REPORT
SUMP
ALARM
M3
M4
M2
RIGHT
M1
LEFT
Pg 7
1.
2.
3.