beautypg.com

Leak testing / console operation, Reports – Franklin Fueling Systems TS-STS Sump Test System Kit User Manual

Page 7

background image

Leak Testing /
Console Operation

Continued...

ACK

SHIFT

SELECT SUMP REPORT

TEST

LEVEL

M1

LEFT

M2

RIGHT

M3

M4

J

W

REPORT

9

SELECT SUMP

SUMP 1

SUMP 2

SUMP 3

ALL

M1

LEFT

M2

RIGHT

M3

M4

SELECT ALARM TYPE

SYSTEM

SUMP

ALL

M1

LEFT

M2

RIGHT

M3

M4

SELECT (SYSTEM / SUMP) ALARM STATUS

ACTIVE

CLEARED

HISTORY

M1

LEFT

M2

RIGHT

M3

M4

6.)

To view an alarm/warning,

press

the

M1

or

M2

Key under the

word Alarm / Warning. While viewing the alarm,

press

the

ACK

SHIFT

key at the keypad to acknowledge.

Cleared and

transient alarms should be acknowledged prior to starting
another test.

7.)

Press

the

Report

key at the keypad to show various report

choices.

— ❖ —

Reports

4

INCON

INTELLIGENT CONTROLS INC.

P.O. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

12:15 PM

SUMP LEAK TEST REPORT

SUMP 2

TEST STARTED

12:00 PM

TEST STARTED

10/31/01

BEGIN LEVEL

7.0230 IN

END TIME

12:15 PM

END DATE

10/31/01

END LEVEL

7.0209 IN

LEAK THRESHOLD

0.002 IN

TEST RESULT:

FAILED

Reports can printout automatically or on
demand from the keypad. The
Sump Leak Test

and Alarm

Reports print automatically.
The other reports, such as
the Sump Level Reports,
Alarm Reports, and Sump
Test Reports can be printed
on demand.

Press the menu select keys
and choose the type of report
that you wish to printout.
Alarm reports will print as
soon as an alarm is detected.
Leak test reports print
automatically after the leak test is finished.

Note that

when a new leak test is complete the data will
overwrite a previous result.

Of the three reports shown here, one is a Level
Summary report and two are Sump Leak Test
Reports.

Up to 4 sumps can be leak-tested at the same
time.

REPORTS continued...

INCON

INTELLIGENT CONTROLS INC.

P.O. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

12:15 PM

SUMP LEAK TEST REPORT

SUMP 1

TEST STARTED

12:00 PM

TEST STARTED

10/31/01

BEGIN LEVEL

2.0120 IN

END TIME

12:15 PM

END DATE

10/31/01

END LEVEL

2.0120 IN

LEAK THRESHOLD

0.002 IN

TEST RESULT:

PASSED

INCON

INTELLIGENT CONTROLS INC.

P.O.. BOX 638

SACO ME 04072

1-800-984-6266

10/31/2001

11:58 AM

SUMP LEVEL REPORT

SUMP 1

2.012 IN

SUMP 2

7.201 IN

SUMP 3

3.218 IN

SELECT REPORT

SUMP

ALARM

M3

M4

M2

RIGHT

M1

LEFT

Pg 7

1.

2.

3.