Help windows – Xylem IM131R01 AQUAVAR AV II User Manual
Page 79

78
Help Windows
Window text
Help Text
Regulation Mode (Normal Default)
Pumping regulation mode, normal or inverse.
See page 64.
Start Value
Start value, allows pressure to drop in system
PSI or Selected Units
before unit starts. (Disabled is default) See page 64.
Config. 2nd Required Value
Configuration of a second value from another
Off (Default)
sensor. See page 64.
Relay Configuration
Relay configuration. See page 64.
Run Motor (Default)
Submenu
Submenu offset: to enter push “ “ key
Offset
for at least two seconds.
Offset Input
Selection of offset input, if required.
Off (Default)
See page 49.
Level 1
Start level for offset 1.
XX.X %
See page 50.
Level 2
Start level for offset 2.
XX.X%
See page 50.
Intensity 1
Intensity of offset 1.
XX.X%
See page 51.
Intensity 2
Intensity of offset 2.
XX.X%
See page 51.
Submenu
Submenu seq. control; to enter push “ “ key
Seq. Control
for at least two seconds. See pages 52 and 53.
Pressure Incr.
Pressure increment at switching of additional pumps
4 PSI
in multicontroller mode. See pages 52 and 53.
Pressure Dec.
Pressure decrement for consecutive pumps.
4 PSI
See pages 52 and 53.
Enable Seq. Ctl.
Frequency limit enable sequence control. Starts
58 Hz (Default)
second pump in multicontroller. See page 55, step 9.
Switch Interval
Time interval pump sequence change. Allows
12h (Default)
multiple pumps to lead/lag in system, based on
switch interval time. See page 55, step 10.
*
*