Repair of faults and errors – Xylem IM131R01 AQUAVAR AV II User Manual
Page 73

Repair of Faults and Errors
72
Table 13: AQUAVAR Electrical Fault Codes
(continued)
Fault Code
Fault Name
Possible Cause(s)
How to Recover
16
Motor Over Temp The drive’s motor temperature
Decrease motor loading. If the
(Fault)
model detected motor
motor is not overheated, check
overheating severe enough to
the temperature model
cause a fault.
parameters.
17
Output Fault
The output sensor detected
• Check motor wiring.
an error.
• Check for and remove any
capacitive load.
• Check the motor and cabling
for shorts to ground.
18
Overcurrent
The drive has measured
• Check the load, motor size,
excessive current in the motor
and cables.
output. This may be caused by: • Review the settings for
• Sudden, heavy load increase.
acceleration and deceleration
• Short circuit in the motor
times.
cables.
• Unsuitable motor.
19
Drive Over Temp
Temperature of the drive’s
• Check the air flow.
heatsink is too high.
• Check that the heatsink is not
clogged.
• Check the ambient
temperature.
• Check that the switching
frequency is not too high
compared to ambient
temperature and load.
20
Motor Overload
Excessive load on the motor
Check the motor and load.
(for example, a jammed load.)
21
Drive Under Temp • Temperature of the drive’s
• Increase the ambient
heatsink is below 0ºC (32ºF).
temperature.
• Ribbon cable not correctly
• Ensure that the ribbon cable is
seated between the power
correctly seated.
and control boards.
22
Motor Stall
The motor’s stall protection
Check the motor.
(Fault)
sensed a stall severe enough
to cause a fault.