Installation procedures, Electrical connections continued, Considerations for control wiring – Xylem IM131R01 AQUAVAR AV II User Manual
Page 19

Electrical Connections continued
• Use circuit breakers on the incoming power lines.
• Grounding must be in accordance with NEC and CEC. If multiple AQUAVAR controllers are
installed near each other, each must be connected to ground. Take care to not form a ground
loop. Maintain a common ground.
• Wire must be made of copper and rated 60 / 75ºC (unless otherwise specified in the table
below). Refer to Tables 4, 5 and 6 for recommended wire gauges and temperature ratings.
Considerations for Control Wiring
Control wiring refers to the wires connected to the control terminal strip. Select control wiring
as follows:
• Shielded wire is recommended to prevent electrical noise interference from causing improper
operation or nuisance tripping.
• Use only UL™ recognized wire.
• Wire voltage rating must be at least 300 V for 230 Vac systems.
Installation Procedures
18
Model
Wire Size 208 Vac
Wire Size 230 Vac
Number
AWG
mm
2
AWG
mm
2
AV2V2S010D
14
2.5
14
2.5
AV2V2S020D
12
4.0
12
4.0
AV2V2S030D
10
6.0
10
6.0
AV2V2S050D
8
10.0
8
10.0
AV2V2S075D
6
16.0
6
16.0
AV2V2S100D
4
25.0
4
25.0
AV2V20010D
14
2.5
14
2.5
AV2V20020D
14
2.5
14
2.5
AV2V20030D
12
4.0
14
2.5
AV2V20050D
10
6.0
10
6.0
AV2V20070D
8
10.0
8
10.0
AV2V20100D
8
1
10.0
1
8
10.0
AV2V20150D
6
1
16.0
1
6
1
16.0
1
AV2V20200D
6
1
16.0
1
6
1
16.0
1
(1) Use wire rated 90ºC in an environment where the ambient temperature is greater than 40ºC (122ºF).
Table 4: Recommended Wire Gauges (230 Vac Models)