Electrical Connections continued
Typical Power Connections
Diagram 5 shows the terminal connections for line power and motor output. See Step 8 for input
line requirements.
Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V or T3/W) back
to an input phase (L1/R, L2/S or L3/T).
As shown in Diagram 5, it is necessary to provide fuses and a disconnect switch for the input AC
line in accordance with all applicable electrical codes. The drive is able to withstand a 110% over
load for 60 s. For maximum protection of the drive, use the fuses listed in Tables 9, 10 and 11
found below and on the next page. The recommended supplier is Bussman.
Table 9: Recommended Fuses (230 Vac Models)
Fuse Size 208 Vac
Fuse Size 230 Vac
Model Number
JJS/JJN
1
JJS/JJN
1
AV2V2S010D
15
10
AV2V2S020D
20
20
AV2V2S030D
30
30
AV2V2S050D
45
45
AV2V2S075D
60
60
AV2V2S100D
80
80
AV2V20010D
10
6
AV2V20020D
15
10
AV2V20030D
20
15
AV2V20050D
30
25
AV2V20075D
40
35
AV2V20100D
50
40
AV2V20150D
70
60
AV2V20200D
70
60
(1) For sizes up to and including 30 A, KTK fuses may be substituted.
Installation Procedures
22
AV2V Drive
Motor
Fuses
Disconnect
Switch
Three-Phase
AC P
ower
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
GND
GND
Diagram 5: Connections for Power Wiring
- 19-001-290B Residential Fire Pump Package (10 pages)
- 1580 Series In-Line Mounted Centrifugal Fire Pumps AC2516 (8 pages)
- A-C Fire Pump Temporary Storage of Equipment – GI-2 (1 page)
- 8100 Series Centrifugal Pumps AC2515 REV.C (63 pages)
- 1580 Series In-Line Mounted Centrifugal Fire Pumps AC2516 REV.B (8 pages)
- 8200 Series Base Mounted Centrifugal Fire Pumps AC2675 REV.C (38 pages)
- A-C Fire Pump – Vertical Turbine Fire Pump AC8499 (28 pages)
- 9100 Series Base Mounted Centrifugal Fire Pumps AC8585 REV.C (37 pages)
- 2000 Series Frame Mounted Pumps AC8652 REV.C (20 pages)
- 19 001 200 R2 SILENT STORM VFD Pumping System (38 pages)
- 19 001 251 R3 Floboy VFD Pumping System (40 pages)
- 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual (162 pages)
- 19 001 351R2 PACE Integrated Pump Controller Human Machine Interface (HMI) for the Silent Storm VFD Pumping System – User Guide (28 pages)
- 19-001-350R2 PACE Integrated Pump Controller Human Machine Interface (HMI) for the Silent Storm VFD Pumping System – Technician Guide (54 pages)
- 6 71 075 004A Autocirc Instant Hot Water Pump E1 BCANCT1W 06 (8 pages)
- 6 71 075 108A ecocirc E Series E10 Bronze Pumps (4 pages)
- 6 71 075 109A Autocirc Instant Hot Water Pump Model ACT E10 (8 pages)
- 6 71 075 145B ACT-4 Potable Hot Water Recirculating Systems (28 pages)
- A 00 091 376A Series E1 and E3 Instant Hot Water Recirculating Systems (6 pages)
- A 00 091 392A Automatic Plug-In Timer for E1_E3 Circulators (2 pages)
- IM 17A ecocirc D5 Vario, Strong and Solar (4 pages)
- IM 23A Electronic Cooling Pump Series DDC (4 pages)
- BMAID R4 (52 pages)
- IM116 R04 4 Submersible Pumps (68 pages)
- IM117 R01 5 and Larger Submersible Pump (48 pages)
- IM118 R03 Sump Pumps (40 pages)
- IM125 R02 RJA & RJDS Quick Set (48 pages)
- IM126R02 E-Z Prime Jet Pump Shallow Well Jet Pump (36 pages)
- IM132 R02 RSPA (FSPA) & RJSP Self-Priming Centrifugal Pumps (28 pages)
- IM136 R01 SM Centrifugal Pump (20 pages)
- IM137 R02 GPC Engine Drive Self-Priming Pump (16 pages)
- IM138 R01 HMC Close-Coupled Centrifugal Pump (16 pages)
- IM152R0 Vertical Sump Pump (OBSOLETE) (12 pages)
- IM162 R03 Dewatering Pumps Contractor Dewatering Pump (20 pages)
- IM163 R01 Wastewater Pumps Dewatering, Effluent and Sewage (36 pages)
- IM164 R01 Single Phase, Single Seal Grinder Pump (36 pages)
- IM186R03 Battery Backup Sump Pump (24 pages)
- IM188 R01 SPM_SPH Self-Priming Pumps (24 pages)
- 10 001 247 R2 TechnoForce Package System (34 pages)
- AC2008B Series HSC3 Base Mounted Centrifugal Pump (22 pages)
- AC8584C Series HSCS Base Mounted Centrifugal Pumps (31 pages)
- IM194 R02 GRINDER PUMPS 1 AND 3 11?4 DISCHARGE (36 pages)
- IM196 R01 Explosion Proof Wastewater Pumps Listed Class 1, Groups C and D Hazardous Locations (32 pages)
- IM228 R03 Model e-SV (esv) (64 pages)
- Goulds Water Technology Model e-SV, Vertical Multi-Stage Pumps Repair Stack (4 pages)