Absolute maximum ratings, Electrical specifications – GE Industrial Solutions JNC350R Series User Manual
Page 2

Data Sheet
August 9, 2010
JNC350R Power Modules; DC-DC Converters
18 – 36 Vdc Input; 28Vdc Output; 350W Output
LINEAGE
POWER
2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are
absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in
excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for
extended periods can adversely affect the device reliability.
Parameter
Device
Symbol
Min
Max
Unit
Input Voltage
Continuous
All V
IN
-0.3 40 V
dc
Transient, operational (≤100 ms)
All
V
IN,trans
-0.3 50 V
dc
Operating Ambient Temperature
Please contact your Lineage Power Sales representative
for information on thermal derating when using forced
airflow.
All Ta
-40 85 °C
Operating Case Temperature
(See Thermal Considerations section, Figure 20)
All Tc -40 100 °C
Storage Temperature
All
T
stg
-55 125 °C
I/O Isolation Voltage: Input to Case, Input to Output
All
1500 V
dc
Output to Case
All
500 V
dc
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.
Parameter
Device
Symbol
Min
Typ
Max
Unit
Operating Input Voltage
(see Figure 12 for V
IN, min
when using trim-up feature)
All V
IN
18 24
36 V
dc
Maximum Input Current
All I
IN,max
25 A
dc
(V
IN
=18V to 36V, I
O
=I
O, max
)
Inrush Transient
All
I
2
t
2
A
2
s
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 12μH source impedance; V
IN
=0V to 36V,
I
O
= I
Omax
; see Figure 7)
All
25 mA
p-p
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to being
an integrated part of complex power architecture. To preserve maximum flexibility, internal fusing is not included.
Always use an input line fuse, to achieve maximum safety and system protection. The safety agencies require a fast-
acting fuse with a maximum rating of 30 A (see Safety Considerations section). Based on the information provided in
this data sheet on inrush energy and maximum dc input current, the same type of fuse with a lower rating can be
used. Refer to the fuse manufacturer’s data sheet for further information.