PAGE 32 13 APR 2000 MAN0373-01
CH. 5
5.2
Data Format Specification
Data format [1]:
Integer data (Positive): Min. unit 1
Example) If F15 (Frequency limiter, upper limit)= 60Hz
Since 60 = 003C
H
Data format [2]: Integer data (Positive, negative): Min. unit 1
Example) -20
Since -20 = FFEC
H
Data format [3]: Decimal data (Positive): Min. unit 0.1
Example) If F17 (gain frequency setting signal) = 100.0%
Since 100.0
×
10 = 1000 = 03E8
H
Data format [4]: Decimal data (Positive, negative): Min. unit 0.1
Example) If C31 (Analog input offset adjust, terminal12) = - 5.0%
Since - 5.0
×
10= - 50 = FFCE
H
Data format [5]: Decimal data (Positive): Min. unit 0.01
Example) If C05 (multi-step frequency 1) = 50.25Hz
Since 50.25
×
100 = 5025 = 13A1
H
Data format [6]: Decimal data (Positive, negative): Min. unit 0.01
Example) If M07 (actual torque value)= - 85.38%
Since - 85.38
×
100= - 8538=DEA6
H
Data format [7]: Decimal data (Positive): Min. unit 0.001
Example) If o05 (follow - up side ASR 1 constant) = 0.105s
Since 0.105
×
1000 = 105 = 0069
H
Data format [8]: Decimal data (Positive, negative): Min. unit 0.001
Example) If being -1.234
Since - 1.234
×
1000 = - 1234 = FB2E
H
Data format [9]: Integral data (Positive): Min. unit 2
Example) If P01 (Motor 1 number of poles) =2pole
Since 2 = 0002
H