CHAPTER 3: OPTION CARD CONFIGURATION (USING AF-300 KEYPAD)
3.1
Keypad Functionality
The keypad functions and operations are covered in the drive manufacturer documentation. This
document is concerned only with describing the keypad functions that are used to configure the option
card and effect the option card operation.
3.2
Option Card Configuration Parameters
The following table lists and describes the parameter settings used to configure the Option Card
parameters. As described previously, Genius devices have the capacity to broadcast 128 bytes (64
words) of global data and receive 128 bytes (64 words) of directed data. The Option Card is limited to 24
bytes (12 words) of global data and 20 bytes (10 words) of directed data. The parameter values can be
changed using the instructions found in the drive manufacturer’s documentation.
Table 3.1 – Parameter Settings
Option
Card
Parameter
Description
Valid Input
Values
Default Value (o31 = 255)
o30
Bus Address
0-31 (1-30
typical)
1
o31
Baud Rate
•
0 = 153.6K EXT
•
1 = 153.6K STD
•
2 = 76.8K
•
3 = 38.4K
•
255 = Reset parameters to
default
0-3
255
1 = 153.6K standard
o32
Global Data Length
0 - 12
7
o33
Directed Data Length
0 - 10
4
o34
User Defined Broadcast Data 1
1-254
0;255*
M14 Operating State
o35
User Defined Broadcast Data 2
1-254
0;255*
M06 Actual Frequency
o36
User Defined Broadcast Data 3
1-254
0;255*
M11 Output Current
o37
User Defined Broadcast Data 4
1-254
0;255*
M10 Motor Output
o38
User Defined Broadcast Data 5
1-254
0;255*
M16 Fault Memory 0
o39
User Defined Broadcast Data 6
1-254
0;255*
M07 Actual Torque
o40
User Defined Broadcast Data 7
1-254
0;255*
M01 Frequency Command
o41
User Defined Broadcast Data 8
1-254
0;255*
255
o42
User Defined Broadcast Data 9
1-254
0;255*
255
o43
User Defined Broadcast Data 10
1-254
0;255*
255