Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
eBoost STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
eBoost START
eBoost STOP
The eBoost™ Operation Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 -
Tuesday (as indicated by the eBoost STOP time of weekday d4 - Tuesday).
The eBoost STOP time of weekday d3 - Monday has no effect as it is followed by the eBoost STOP time
of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the eBoost™ Operation Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of
weekday d5 - Wednesday.
The eBoost START time of weekday d5 - Wednesday has no effect as it is preceded by the eBoost START
time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
• Date and Time (first page of parameter).
• eBoost™ screen how many hours of eBoost™ Operation Mode have been selected
for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.