GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual
Page 32

Modifications reserved
Page 32/79
OPM_SGS_USM_M40_M50_2US_V010.doc
User Manual SG Series 400 & 500 UL S2
Code
Alarms
Meaning
4570
OVERLOAD
The UPS-System is in an overload condition >125% on
Inverter, or >150% on Utility.
With Utility unavailable, a sequence of “stop operation”
starts.
Time out depends on Load quantity.
4571
OVERLOAD: LOAD ON UTILITY
With Utility Bypass supply available and load >115%, the
Load is transferred on Utility.
Load will be transferred again automatically on Inverter
when Load <100%.
4581
INVERTER AND UTILITY NOT
SYNCHRONIZED
The voltages of Utility and Inverter are not synchronized,
which causes the opening of K6.
4608
ECO CONFIG FAILURE
The propagation of the eBoost / IEMi configuration to other
units in a Parallel System failed.
4697
BATTERY OVERTEMPERATURE
Detection of Battery over temperature condition.
Can be deactivated by Service Center.
4698
BATTERY POWER INSUFFICIENT
In case of Utility Failure, with the actual Load, the run time
would be below stop operation time (default 3 minutes).
4700
DC LOW
Battery voltage is at the lowest limit.
Will stay Off Inverter until the battery voltage reaches the
value in parameter.
4701
POWER SUPPLY BOARD
FAILURE
Failure detection on the +24V derived from the DC-link
voltage.
4900
LOAD LOCKED ON INVERTER
The Load is locked on Inverter after 3 Load transfers within
30 seconds.
After time out (default 30 seconds) Bypass will be free.
4955
OVERTEMPERATURE
An over-temperature condition has been detected on
Inverter.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.
4998
LOAD OFF DUE TO EXTENTED
OVERLOAD
Load Off after time-out of “stop operation” for overload on
Inverter or Bypass (time depending on the % of overload).
4999
LOAD OFF DUE
TO LOW BATT. OR TEMP.
Load Off after time-out of “stop operation” with missing
Utility due to Battery low voltage or over-temperature
condition.