1 events (alarms and messages), 2 alarms list, Events (alarms and messages) – GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual
Page 29: Alarms list

Modifications reserved
Page 29/79
OPM_SGS_USM_M40_M50_2US_V010.doc
User Manual SG Series 400 & 500 UL S2
6.3.1 Events (alarms and messages)
Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software “GE Data Protection” installed or with the monitoring system “GE Power Diagnostic”.
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the acoustical alarm).
6.3.2 Alarms list
Code
Alarms
Meaning
4000
SETUP VALUES LOST
Parameters are lost and have been replaced with default
values.
Call nearest Service Center for intervention.
4001
REGULATION BOARD FAILURE
A blocked DSP on the Control board causes this alarm, and
consequently the shutdown of Rectifier and Inverter and
the opening of K3.
4004
UPS FAILURE ON PARALLEL
SYSTEM
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
4006
BUS JA CRC FAILURE
The parallel communication bus system is subject to high
errors rate on channel JA.
4007
BUS JB CRC FAILURE
The parallel communication bus system is subject to high
errors rate on channel JB.
4008
BUS JA FAILURE
There is an interruption in the channel JA of the parallel
communication bus system.
4009
BUS JB FAILURE
There is an interruption in the channel JB of the parallel
communication bus system.
4010
CONNECTIVITY BUS FAILURE
The connectivity communication bus is faulty or
interrupted.
4100
RECTIFIER FUSES FAILURE
The u-switch mounted on the Rectifier Input Fuses
indicates a blown fuse, and consequently shut down.
Clearance of this condition allows you to restart the
Rectifier.
4102
K4 CLOSING FAILURE
K4 not closed despite a closing command being issued.
Signaled by auxiliary contact.
Rectifier cannot start.
4103
K4 OPENING FAILURE
K4 not open despite an opening command being issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier Bridge.
4104
BATTERY FUSES FAILURE
This function, when enabled on input programmable
relays (password required), warns the user about the
external Battery Fuses failure or MCCB opening, signaled
by NO free contact.
4105
RECTIFIER OVERTEMPERATURE
Temperature sensor indicates an over temperature on the
Rectifier Bridge.
Only alarm is given.
The Rectifier, when in Off state, cannot start as long as this
condition persists.