GE Industrial Solutions SG Series 400 & 500 Operating Manual User Manual
Page 41

Modifications reserved
Page 41/79
OPM_SGS_USM_M40_M50_2US_V010.doc
User Manual SG Series 400 & 500 UL S2
To better understand the eBoost™ programming modes, some typical examples are shown:
Example 1:
For continuous eBoost™ Operation Mode set the eBoost START times to 00:00 and the eBoost STOP
times to 23:59 for all weekdays, but almost 1 day must have 1 minute of VFI programmation: i.e d2 -
Sunday 00:00 to 23:58).
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 00:00 00:00 00:00 00:00 00:00
eBoost STOP
23:59 23:58 23:59 23:59 23:59 23:59 23:59
Example 2:
eBoost STOP before eBoost START.
eBoost START 18:00, eBoost STOP 06:00 for weekday d4 - Tuesday.
Means that on d4 - Tuesday the eBoost™ Operation Mode is active between 00:00 and 06:00 and
between 18:00 and 23:59.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 00:00 18:00 00:00 00:00 00:00
eBoost STOP
23:59 23:59 23:59 06:00 23:59 23:59 23:59
Example 3:
eBoost™ Operation Mode during the night and week-end.
If the eBoost™ Operation Mode must be enabled all nights (d3 - Monday ÷ d7 - Friday) between 18:00 in
the evening and 06:00 of the following morning and during all Saturday (d1) and Sunday (d2), the
corresponding parameters are:
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 18:00 18:00 18:00
eBoost STOP
23:59 23:59 06:00 06:00 06:00 06:00 06:00
Example 4:
If the eBoost™ Operation Mode must be enabled on Monday (d3) and Tuesday (d4) between 18:00 in the
evening and 06:00 of the following morning, on Friday (d7) between 12:00 and 13:00, during all Saturday
(d1) and on Sunday (d2) until 20:00, the corresponding parameters are.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
eBoost START
00:00 00:00 18:00 18:00 00:00 00:00 12:00
eBoost STOP
23:59 20:00 23:59 06:00 06:00 00:00 13:00
eBoost START
eBoost STOP
In dark color are displayed the times with eBoost™ Operation Mode.
The arrows indicate the conditions given by the eBoost START and eBoost STOP times introduced with
the parameters.
Note that on day d6 - Thursday the interval has length 0 (zero), therefore the eBoost™ Operation Mode
is not enabled on this day.