User Manual SG Series 225 & 300 UL S2
Code
Message
Meaning
4534
MULTIPLE LOAD TRANSFER
2 transfers Inverter- Utility have been detected in a short
time, (default 30 seconds).
4535
BYPASS LOCKED
Bypass is not available.
Contactor K6 is open, SSM deactivated.
4536
BYPASS FREE
Bypass is enabled.
Contactor K6 is closed.
4561
LOAD OFF
The “Load Off” key on the UPS Control Panel has been
pressed, with the output circuit switch Q1 closed.
4562
DETOUR ON
The auxiliary contact indicates that External Maintenance
Bypass has been closed.
4564
DETOUR OFF
The auxiliary contact indicates that External Maintenance
Bypass was opened.
4567
COMMAND LOAD ON UTILITY
The control unit received a command to transfer the Load
on Utility.
4568
COMMAND LOAD ON INVERTER
The control unit received a command to transfer the Load
on Inverter.
4572
NO MORE OVERLOAD
End of the overload condition detected with alarm 4570.
4580
INVERTER AND UTILITY
SYNCHRONIZED
The voltages of Inverter and Utility Bypass are
synchronized.
4582
COMMAND NOT TO
SYNCHRONIZE
Command not to synchronize with Utility.
4583
COMMAND TO SYNCHRONIZE
Command to synchronize with Utility.
4600
COMMAND UPS ON
The eBoost™ Operation Mode has been disabled or the
programmed time is expired.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.
4601
COMMAND UPS STANDBY
The eBoost™ Operation Mode is enabled, and according to
the time program the UPS will run in eBoost™ Operation
Mode, supplying the Load normally by Utility.
4602
Q1 OPEN
The auxiliary contact indicates that the output switch Q1
has been opened.
4603
Q1 CLOSED
The auxiliary contact indicates that the output switch Q1
has been closed.
4604
COMMAND IEMi ON
The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will run in
IEMi mode.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the
programmed time is expired.
4606
eBoost ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation of the
functions.
4607
eBoost ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation Mode will be
temporarily inhibited.