GE Industrial Solutions SG Series 225 & 300 Operating Manual User Manual
Page 27
![background image](/manuals/295674/27/background.png)
Modifications reserved
Page 27/79
OPM_SGS_USM_M22_M30_2US_V010.doc
User Manual SG Series 225 & 300 UL S2
`
Home\Meter
COUNTERS
Bypass utility failure
:
25
Rectifier utility failure
:
14
Overloads :
15
InvOperTime [h]
:
2135
UPSOperTime [h]
:
3125
eBoost OperTime [h]
:
1379
Statistics screen
The total number of bypass utility faults (bypass utility out
of tolerance).
The total number of rectifier utility faults (rectifier utility out
of tolerance).
The total number of detected output overloads.
The total operating time for the Inverter (in hours).
The total operating time for the UPS (in hours).
The total operating time for the UPS in eBoost™ Operation
Mode (in hours).
This counter is displayed only when eBoost™ Operation
Mode is available (option).
`
Home\Meter
BATTERY DISCHARGE COUNTERS
Residual Charge Level
100-81% 81-51% 50-21% 20-0%
15 7 3 1
On Battery Time [h]: 15
Statistics battery discharge screen
Residual Charge Level
The number of discharges combined with the percentage
of the available residual battery capacity at the time utility
power is restored.
On Battery Time [h]
The total operating time of the UPS on battery (in hours).
`
Home\Meter
UTILITY
NUMBER OF FAST TRANSIENTS
<2ms >2ms >5ms
>10ms
25
20
7
5
eBoost rate
=
70 %
eBoost™ Operation Mode statistic screen
This screen is displayed only when eBoost™ Operation
Mode is available.
The number of fast transients occurred on the bypass utility
on the last seven days.
The statistic evaluation in % (100= good; 0= bad) of the
utility, for the eBoost™ Operation Mode.