Installation Guide LP 33 Series 50-60 kVA
EPO (Emergency Power Off)
An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on
terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 4.4-1 / X2 & J2).
7
89
10
11
22
21
20
19
18
7
J2
X1
2
1
JP3
X2
Fig. 4.4-2 PCB Customer Interface
Fig. 4.4-3 PCB P1 – Control board
NOTE !
To enable this function, remove jumper JP3 on the Customer Interface and the
cable on the terminal X2 / 1, 2 (see Fig. 4.4-2).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP5 on the P1 – Control
board are OFF (see Fig. 4.4-3).
In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit.
When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.
NOTE !
This procedure could imply a load shutdown.
When the EPO has been activated, the system must be restored as following:
x
Press the push-button EPO (contact on X2 / 1, 2 is closed again).
x
Perform the command INVERTER OFF entering the screen:
MENU/COMMAND MENU/INVERTER OFF.
COMMAND MENU
INVERTER ON
INVERTER OFF *
x
Start the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON.
COMMAND MENU
INVERTER ON *
INVERTER OFF